1 clearances, 0 general (cont'd), 0 location – Reznor RDF Unit Installation Manual User Manual

Page 4: 0 uncrating/ preparation, 0 clearances and dimensions, 4 installation codes/requirements (cont'd)

Advertising
background image

I-RDF, PN148384R5, Page 4

Codes for Special Installations: (1) Aircraft Hangar -- Installation in an aircraft han-

gar must be in accordance with the Standard for Aircraft Hangars, ANSI/NFPA 409 (lat-

est edition) or CAN/CGA B149 Installation Codes; (2) Public Garage -- Installation in a

public garage must be in accordance with the Standard for Parking Structures, ANSI/

NFPA 88A (latest edition) or the Standard for Repair Garages, ANSI/NFPA 88B (latest

edition) or in Canada with CAN/CGA B149 Installation Codes.

1.0 General

(cont'd)

1.4 Installation Codes/Requirements (cont'd)

2.0 Location

Location must comply with clearances in Paragraph 4.1. Makeup air should enter at

the highest point practical. By doing this, the fresh air will entrain dust laden air at the

ceiling and move it toward the point of exhaust. Also, fresh air directed downward from

the roof or ceiling will mix with hot ceiling air resulting in improved distribution of heat

in the building.
Always introduce fresh makeup air so that it moves across the greatest distance within

the room or building before reaching an exhauster.

3.0 Uncrating/

Preparation

Immediately upon uncrating the unit, check the gas specifications and electrical volt-

age (system rating plate is in the control compartment) to be sure that they agree with

the supply at the installation site. Check for any damage that may have been incurred

during shipment. If damage is found, document the damage with the carrier and con-

tact your distributor.
The following control parts are

shipped loose inside the unit:

• a 3-position control switch mounted in a 4x4 junction box (except units with Option

AG37) NOTE: If an optional remote console is ordered, this switch is mounted on

the console; the console is shipped separately.

Depending on the gas and/or air controls selected, the following additional parts are

shipped inside the unit or separately.

Gas Controls

Shipped-Loose Parts

Options AG30, AG32, AG33,
AG47, AG48

*Remote Temperature Selector

Option AG31

*Remote Temperature Selector, Space Override Thermostat

Option AG36

Remote Console

Air Controls

Shipped-Loose Parts

Option AR19, AR22

*Potentiometer

Option AR20, AR23

Remote Pressure Sensor

Option AR32

Toggle Switch

Option AR36

Photohelic Pressure Sensor

Option AR37

Photohelic Pressure Sensor

*If an optional remote console is ordered, these controls are mounted on the console.

The console is shipped separately.

On all sizes with an

optional dirty filter switch, the tubing and clamps are shipped

inside the cabinet.

Be sure that all shipped-separate accessories for the installation are available. Other

shipped-separate accessories could include a roof curb, a remote console, an outside

air hood, a disconnect switch, and/or an indoor filter cabinet.

4.0 Clearances

and

Dimensions

4.1 Clearances

Clearances - inches (mm)

Top

Control Side Side Opposite

Controls

Bottom

To Combustibles

To Non-Combustibles

3 (76) Width of unit

3 (76)

3 (76)

0 - Curb

Clearance to combustibles is defined as the minimum distance from the heater to a

surface or object that is necessary to ensure that a surface temperature of 90°F above

the surrounding ambient temperature is not exceeded. In order to service the system,

the minimum clearance on the control side of the unit must be equal to the width of the

unit.