Carrier 19CB User Manual

Page 10

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

• ^^>4-iXwCr.- ••VJ '

ava

>

;

«O*«®

a.

b.

9. If

Fig. 7 — Capacity Control Module

(Electronic Control)

Check the foregoing motor current calibrations
with machine under “Auto.” control as
follows'

Close vanes manually (capacity control to
“Dec”).
Turn capacity control to “Auto.” Vanes
should stop opening at electrical demand
setting.

control was calibrated at less than 100%

load, turn electrical demand adjustment setting
to 100%. Control is now automatically cali­
brated for 100% full load current.

10. If control cannot be calibrated with above

procedure, check voltage signal from signal
resistor in starter. At 100% full load current,

voltage between terminals 23 and 24 inside

control center must be 0.5 ± 0 . 1 volts. If not
in this range, check sizing of resistor in starter.

Both excess motor current and chilled water

temperatures below the thermostat set point (Fig.
7) will override the capacity control setting. If the
capacity control knob is in the “Inc” position, the
guide vanes will stop opening. With the knob in any
of the other positions, the vanes will close as needed.

The motor current hmiting circuit operates in

2 steps.

At 100% full load motor current, the vanes

will stop opening further. If the motor current
should increase to 105% due to some change in
load conditions, the vanes will close until the
motor current is reduced to about 102%.

If the motor current is reduced to 98% or

below, control again operates in response to chilled
water temperature.

The electrical demand adjustment permits the

operator to set the maximum current drawn by the
motor and thus minimize the electrical demand

rate during off-season operation.
CHILLED WATER CALIBRATION (Electronic
Controls)

1. Turn throttle range adjustment (Fig. 7) fully

clockwise.

2.

Turn chilled water thermostat until design

chilled water temperature is maintained. Mark
thermostat at this position. If capacity control

vanes hunt, turn throttle range adjustment

counterclockwise in small increments until

hunting ceases. Chilled water thermostat may
require resetting.

Setting Operating Controls — Pneumatic Capacity
Control

PILOT POSITIONER

ITEM

DESCRIPTION

1

MAIN AIR CONNECTION (25 PSIG)

2

STARTING POINT ADJUSTMENT NUT

3

LEVER ARM

4

FOLLOWER SPRING

5

PILOT AIR CONNECTION

(FROM CONTROL CENTER)

Preparation:
a. Place jumper between field wiring terminal

and load limiting module terminal*^.

b. Open 25 lb air supply valve.
c. Remove cover from pilot positioner.

Calibration:

Rotate dial on chilled water thermostat to vary

pilot pressure. Observe pressure gage in pilot
supply line near pilot positioner and adjust starting
point nut (2) until piston operator begins to move
at 5 psi pilot pressure. Place follower spring (4) in
proper hole in level arm so that piston operator
opens 100% at 15 psi pilot pressure.
Completion:

Remove jumper from terminals and

Replace cover.

10