Check operation of safety controls — as the, Off on, N□ □ n – Carrier 19CB User Manual

Page 6

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

Check Starter

— Before starting the 19CB machine,

open the main disconnect and check starter.

1. Remove contactor arc chutes. Be sure con­

tactors move freely and that shipping string has
been removed. Replaee arc chutes.

2.

Check contactors for dirt and rust. Clean

contact magnet surfaces lightly with sandpaper.
Do not sandpaper or file silverplated contacts.
Apply a very thin coat of petroleum jelly to
magnet surfaces and then wipe it off. If starter
has been in a dusty atmosphere, vacuum clean
the cabinet and wipe with hnt-free cloth.

3. Remove fluid cups from magnetic overload

relays. Add dashpot oil to cups per instructions
on relay nameplate. Oil is slripped in small vials
usually attached to starter frame near the
relays. Use only dashpot oil supplied with
starter. Do not substitute. Overload relays are

factory set for 108% of motor full load
amperage. Resetting is not normally required,
nor is it recommended except by a qualified
electrical shop.

4. Check transfer timer for proper setting. On

Star-Delta starter, timers have adjustable range
of 10 seconds to 3 minutes and are factory set
for 1 minute. Auto.-Transformer timers have
adjustable range of 1 to 60 seconds and are
factory set at 30 seconds.

5. With main disconnect open, manually open and

close the main control relay (ICR) to be sure it
operates freely.

Check Operation of Safety Controls

— As the

following checks are made, control panel lights
should appear as indicated in the diagrams.

OFF

ON

1

.

Open main disconnect (all

power off to starter and
controls).

Disconnect

main

motor

leads

in

starter.

2.

Provide control circuit

power

from

separate

115-volt source.

n

ON

STOP

START

OIL

PUMP

n

□ □

n

POUVER SAFETY

LOAD

CIRCUIT RECYCLE

PROGRAM

TIMER

ON

STOP

START

OIL

PUMP

■ □ □

n

POWER

SAFETY

LOAD

CIRCUIT RECYCLE

PROGRAM

TIMER

n

ON

STOP

START

OIL

PUMP

■ ■

n

POWER

SAFETY

LOAD

CIRCUIT RECYCLE

PROGRAM

TIMER

3. Press ON-STOP button

(light

goes

on).

If

SAFETY CIRCUIT light
does not go on, check
resets on condenser high-
pressure safety, low-refrigerant temperature
safety, bearing and motor Ihgh-temperature
circuit breakers and compressor overloads in
starter. Check 3-amp fuse in control center.

If SAFETY CIRCUIT light goes on but

LOAD RECYCLE light stays off, check the
chilled water recycle switch (auto-reset).

If both lights go on, manually trip and reset

motor and bearing high-temperature circuit
breakers, compressor motor overloads in
starter, and low-refrigerant temperature cutout
to be sure they cut off the safety light.

Tripping the chilled water recycle switch will

cut off the LOAD RECYCLE light only.

4. Press ON-STOP button

(light goes out). Remove
and tag gray striped wire
from

control

center

terminal

5. Start chilled water and

condenser water pumps.

Press ON-STOP button
(light goes on).

ON

STOP

START

OIL

PUMP

■ □ □

n

POWER

SAFETY

LOAD

CIRCUIT'RECYCLE

PROGRAM

TIMER

ON

STOP

START

OIL

PUMP

■ □ □

n

POWER SAFETY

LOAD

CIRCUIT RECYCLE

PROGRAM

TIMER

6. Press OIL PUMP button

for several seconds. Pump
should raise oil pressure

16 - 18 psi above refrig­

erant pressure at machine
shutdown condition. SAFETY CIRCUIT and

LOAD RECYCLE lights should go on.

ON

STOP

START

OIL

PUMP

■ ■

n

POWER

SAFETY

LOAD

CIRCUIT RECYCLE

PROGRAM

TIMER

ELECTRONIC CONTROL

PNEUMATIC CONTROL

Fig. 6 — Control Center Components

7.

Release

OIL

PUMP

button.

SAFETY

CIR­

CUIT light and LOAD
RECYCLE light should go
out.

n

ON

STOP

START

OIL

PUMP

□ □

n

POWER SAFETY

LOAD

CIRCUIT RECYCLE

PROGRAM

TIMER

Advertising