background image

knob on demand limit control at 100% and turn

calibration screw fully clockwise.

Place a clamp-on ammeter on one of the 3

starter leads. Be sure ammeter scale is set so that
compressor full load amperage will register be­
tween midway and just under the top of the scale.

Install jumpers between ^ and [^, and

between

and

11

Close disconnects, start

compressor and check oil pressure and temperature
(Fig. 2). With compressor running, operate the

guide vanes with capacity control switch or pneu­
matic thermostat. Do not exceed 100% full load

amps.

1. Check controls 1 and 2 as indicated in Table 4.

2.

Stop machine, open disconnects, remove

jumpers and check controls 3, 4 and 5 as

indicated.

Table 4 — Setting Safety Controls

SAFETY OR CONTROL DEVICE

1. Chilled Water Low-Temperature Cutout and Recycle Switch

(Fig. 1)

'TEMPERATURE AD.IUSTMENl

^ O,

DIFFERENTIAL ADJUSTMENT

JZ, —’ ''Bi*

Set this switch to break at approximately 5 F below design

chilled water temperature, or at 36 F whichever is higher

Set the differential at 10 ± 1 F so that when the machine shuts

down

automatically

at

approximately

5

F

below

the

design

chilled water temperature it will restart at approximately 5 F

above the design water temperature.

This

control

must

break

ahead

of

the

refrigerant

low-

temperature

cutout

switch

or

the

machine

will

not

recycle

automatically

2.

Refrigerant Low-Temperature Cutout (Fig. 6)

CUTOUT

ADJUSTMENT

Set refrigerant low-temperature cutout at 33 F or one degree below

design

refrigerant

temperature,

whichever

is

lower,

while

checking

temperature at thermowell near control center

SAFETY OR CONTROL DEVICE

STOP

MACHINE,

REMOVE

JUMPERS

AND

PEREORM

RE­

MAINING CHECKS.

3.

Condenser High-Pressure Cutout (Fig. 6)

CUTOUT ADJUSTMENT .f.'

COVER

JiEFRlG

ii

114

SETTING

15 psig

45 psig

RESET
BUTTON

CUTOUT SCALE

The

condenser

high-pressute

cutout

is

factory

set

to

shut

the

machine

down

when

condenser

pressure

reaches

setting

listed.

Isolate the switch and check setting with a metered supply of air

4. Oil Heater Thermostat (Fig. 2)

Set the oil heater thermostat to maintain a minimum oil reservoir

temperature of 140 F at shutdown.