Table 4 — setting safety controls (contd), Setting operating controls — electronic, Pressure – Carrier 19CB User Manual

Page 9: R- vl

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

SAFETY OR CONTROL DEVICE

Table 4 — Setting Safety Controls (contd)

SAFETY OR CONTROL DEVICE

5. Low Oil Pressure Cutout (Fig, 2)

RESERVOIR

PRESSURE-:^,

RANGE

^

DIAL ADJUSTMENT,
REMOVE METAL

COVER

DIFFERENTIAL-

OIL

PRESSURE

Low oil differential pressure switch is factory set to open at 5 5 ± 1

psi and close at 12 5 ± 1 psi differential pressure Operate oil pump

manually Remove cap and gasket from regulating valve and loosen

locknut

Turn

adjusting

screw

counterclockwise

to

lower

oil

pressure to 5 psi differential If safety does not trip, turn range dial

clockwise until cutout occurs

6. Oil-Pressure Regulating Valve (Item 6, Fig

2

) .

REFRIG

^ R- Vl.

R-114

SETTING*

1 5 psid

15-20 psid

^Settings given are above

reservoir pressure

SEALING

GASKET'

Remove cap and washer and loosen locknut Turn adjusting screw

clockwise to raise oil pressure

7. Vane Speed Valve (Electronic Machine Only)

Angle valve is located between oil line to main bearing and "F" and

"G" solenoid valves (Items 8 and 9, Fig 2) Set valve at full open

position

8. Chilled Water Flow Switch

Field

supplied

and

ir-rstalled

Follow

switch

manufacturer's

instruc­

tions for adjustment and maintenance

9. Main Bearing Oil Temperature (Item 14, Fig. 2).

During

machine

operation,

gage

should

read

145-160

F

Adjust

water flow thnr oil cooler with plug cock (item 11, Fig. 2) Do not

exceed 7 gpm or pressure drop of 5 psi Do not exceed 200 psig

working pressure

10.

Dual Pressurestat for R-114 Pump-Down Compressor

COVER

LOW-PRESSURE

SWITCH

COMPRESSOR

CONNECTIONS'

CUTOUT AND

CUT-IN PRESSURE

ADJUSTMENT

HIGH-

PRESSURE

SWITCH

CUT-IN

PRESSURE

'ADJUSTMENT ONLY

CUTOUT PRESSURE
ADJUSTMENT ONLY

High-pressure switch to open on rise at 45 0 psig Low-pressure

switch to open on fall at 2 0 in Hg vacuum

Set

high-pressure

switch

by

operating

compressor

and

throttling

pump-down condenser water while watching pressure gage

Set

low-pressure

switch

by

operating

compressor

and

gradually

shutting suction valve while watching pressure gage

Setting Operating Controls — Electronic

MOTOR CURRENT CATIBRATION (Electronic
Capacity Control)

1. Establish a steady motor current value for this

calibration.

Open

guide

vanes

manually

(capacity control to “Inc”) until full load
current is reached. Motor current calibration
(Fig. 7) may need to be turned counterclock­
wise to permit vanes to open further. Do not

exceed 105% of nameplate full load amperes.

If system load is sufficient to maintain full
load current for a period of time, calibrate at
this condition. With small loads, pull down to
and maintain design leaving chilled water
temperature (capacity control at “Hold”) and

calibrate at this condition.

2. Measure motor current at selected condition.

Determine its percentage of full load motor
current.

3. Use this percentage figure to set the electrical

demand adjustment (Fig. 7) per the following
table:

Percent of Full

Load Motor Current

105

85 or above

65 to 84

45 to 64

below 45

Electrical Demand

Adjustment Setting

100

%

80%

60%

40%

Control cannot be

calibrated

4. Turn the motor current cahbration adjustment

fully clockwise. The guide vanes will close part
way.

5. Turn the thermostat adjustment (Fig. 7) to

“Cooler” (fully counterclockwise).

6. Set capacity control at “Inc

7

position.

Slowly turn the motor current calibration
counterclockwise. Allow the guide vanes to
open until motor current reaches 5% above the
electrical demand setting.

NOTE: There is a time lag of several seconds
due to feedback capacitance in the motor
current circuit. When the motor current cali­

bration setting is adjusted, allow for this time

lag.

Advertising