ADVANCED SETUP

32

NOTE: You can exit Advanced Setup at any time. When exiting, you

will be prompted to save changes if you have made any. Select

“YES” to save your changes, “NO” to revert back to

previous settings.

Cooling Humidity

1

Open the door of the Evolution

®

Control.

2

Press the ADVANCED setup button.

3

Press the LEFT button three times to view the COOLING

HUMIDITY screen (4 of 7).

4

Use the Right Up/Down button to set your desired humidity level.

5

To exit, press ADVANCED or simply close the door.

- OR -

6

If you want to change the way cooling dehumidification is

controlled, scroll to DEHUMIDIFY. You will have two options.

OFF – The system will not activate the cooling equipment to

dehumidify if the cooling temperature has been satisfied.

ON – The system dehumidifies by activating the cooling

equipment – even after the cooling temperature has been

satisfied. The system will not cool to dehumidify below 70° F

in order to protect equipment. Your air conditioning system will

provide excellent humidification control with DEHUMIDIFY set to

either ON or OFF

. However, you will receive better humidification

control with the ON setting.

7

Use the Right Up/Down button to make your selection.

8

To exit, press ADVANCED or simply close the door.

NOTE: You can exit Advanced Setup at any time. When exiting,

you will be prompted to save changes if you have made any.

Select “YES” to save your changes, “NO” to revert back to

previous settings.