0020117819_00 - 01/11 - Glow-worm

- 15 -

2.3

Protection against the sharp edges of the sheet metal

for the cable passage (if necessary)

(x1)

2.4

Leak-tight seal for the cable passage (if necessary)

(x1)

3

Packet of documents

(x1)

3.1

Installation manual

(x1)

3.2

Instructions for use

(x1)

4

Command unit

(x1)

• Check the contents of the package.

9.2

Recommendations before installation

9.2.1

Design of the heating circuit

The heat emitters may be either low temperature (underfloor

heating, etc.), or medium temperature (warm radiator, etc.).

b

We recommend that you provide sufficient flow for the

temperature difference between flow and return to

be equal to 7 C for a underfloor heating and 15 C for

radiators.

The route of the piping will be designed to take all measures ne-

cessary to avoid air pockets and facilitate the permanent venting

of the installation. Vents must be provided at each high point of

the pipes, and on all the radiators.

b

Always leave a radiator open.

We recommend installing a drainage valve at the lowest point of

the installation.

In the case of the use of thermostatic valves, it is imperative not

to fit to all radiators, taking care to fit these valves in rooms with

high input and never in rooms where the room thermostats are

installed.

- If it is an old installation, it is essential to rinse the radiator

circuit before installing the new appliance and to add an anti-

sludge filter.

- If a component of the system is not to be installed

immediately, protect the various connections so plaster

and paint cannot compromise the seal on the subsequent

connection.

• Install the following components on the heating circuit return:

- a heating filter,

- 2 quarter-turn shut-off valves (1 each side of the filter),

- an air separator (if necessary),

- an anti-sludge filter (if necessary).

• In the case of a underfloor heating, install a security device to

prevent overheating, with manual reset (55°C) on the heating

circuit flow. Connect the overheating security device to the

glycol pump of the heat pump.

9.2.2

Design of the heat pump circuit

Installation pipework must be designed and installed to ensure

venting of air from the system is possible.

b

Ensure that the water flow rate of the water circuit

corresponds to the nominal water flow rate of the

appliance (see ¨Technical data¨ chapter).

• Install the following components on the rear section of the

heat pump:

- a filter,

- a ¼ shut –off valve on each side of the filter,

- a drain valve,

- an air separator (if necessary)

- a sludge deposit (if necessary).

• Install a ¼ turn shutoff valve in the flow of the heat pump.

i

In order to avoid the transmission of vibrations to

surrounding structures, use flexible hoses for the

hydraulic connections at least 1 metre from the heat

pump.

b

Insulate the pipes with a UV- and hightemperature-

resistant insulation.

9.3

Dimensions

9.3.1

Envirosorb 7

150

150

600

908

326

821