Installation – Glow-worm Clearly Heat Pumps Envirosorb2 User Manual

Page 21

Advertising
background image

0020117819_00 - 01/11 - Glow-worm

- 19 -

Key

1 Heat pump

2 Power supply and electrical protection for the heat pump (*)

3 Command unit for the heat pump

4 Glow Worm control unit (*)

5 Glow Worm hydraulic module (*)

6 Anti-sludge filter (*)

A flow heat pump circuit

b Return heat pump circuit

E

Return heating circuit

f

flow heating circuit

H Discharge from the safety valve to a container for recovering glycol

water solution

(*) Not delivered with the appliance

Adjusting the heat pump's command unit

• To find out the description of each function,

see the chapter "Specific adjustment".

i

The setting of codes 112, 114, 117, 122, 123,

124, 125, 126 must be identical on the heat pump

command unit and the systempro control unit.

Menu

Name of the function

Value

factory setting

100

Type of system regulation

2

2

101

Configuration of the command unit

0

0

104

Test modes

0

0

109

Threshold for protection against frost

0°C

0°C

112

External calibrated adjustment graphs

7 - 12 (*)

8

114

ECO heating mode

1 - 20°C (*)

5°C

116

ECO cooling mode

0°C

5°C

117

External calibrated adjustment graphs for cooling

0 (*)

2

122

Maximum reference exterior temperature

24 - 46°C (*)

40°C

123

Exterior temperature from which the heat pump stops in cooling mode

0 - 30°C (*)

22°C

124

Minimum temperature of water in the installation in cooling mode

4 - 20°C (*)

4°C

125

Maximum temperature of water in the installation in cooling mode

4 - 20°C (*)

12°C

126

Configurations exterior sensor

2

2

147

Configuration of the output between terminal channels 5 and N

1

1

148

Limit exterior temperature (T0)

-20°C

-20°C

149

Choice of display in the command unit's temperature zone

1

1

155

Functioning of main circulator

0

1

(*) Refer to the system installation manual for pairing the settings of these codes.

Application conditions

- Command unit used as configuration tool (see the chapter

"location of the appliance"),

- Installation with underfloor heating (< 53°C) or low-

temperature radiator (<60°C),

i

For the dimensioning of the cables and the electrical

protection on the appliances, see the chapter

"Electrical connection".

INSTAllATION