Installation, 1 access to main board, 2 cable passage – Glow-worm Clearly Heat Pumps Envirosorb2 User Manual

Page 25: 4 electrical wiring

Advertising
background image

0020117819_00 - 01/11 - Glow-worm

- 23 -

The cables connecting the installation's electrical panel and the

heat pump must be:

- Suitable for a fixed installation.

- weather resistant.

- equipped with wires adapted to appliance’s power rating.

• Connect the heat pump to an electrical panel via an

independent protection system (differential breaker with at

least 3 mm between each contact). See the table below.

Additional protection may be required during installation to

ensure buffer category II.

Description

Unit

8

12

15

Electricity supply

V-ph-

Hz

230 - 1 - 50

Acceptable voltage range

V

198/264

Maximum power absorbed

kW

2.7

5.1

5.1

Maximum current

A

14

23

20

Power fuse (gl)

A

15 Type B 25 Type D 25 Type D

Maximum current in glycol

pump

A

2

13.1 Access to main board

B

A

A

A

C

2

1

Key

1 Terminal blocks for 230 V and 12 V connection

2 front panel

• Remove the fastening screws (A).

• Slide the front panel (2) downwards (B) and pull it towards

yourself (B) using the handle.

• To close the appliance, carry out the operations in reverse order.

13.2 Cable passage

e

The low and mains voltage cables must be inserted in

different sleeves.

2

1

Key

1 Mains-voltage cable passage

2 Low-voltage cable passage

• Insert the electrical power cables in passages (1) and (2)

provided for this purpose.

• Make sure that the electrical cables are not in contact with the

compressor and the hot pipes.

• Fix the electrical cables with the clamps installed inside the

heat pump.

13.4 Electrical wiring

3

2

4

1

Key

Recommended cable section

1

230 V power cable

3 x 2.5 mm²

2

12 V cable

0.75 mm²

3

230 V cable (outputs 2A

maximum)

0.75 mm²

4

Connection cable for the

command unit

4 x 0.75 mm²

INSTAllATION