11 fault finding – Glow-worm Ultimate 100FF User Manual

Page 29

Advertising
background image

29

221966B

FUSE
TYPE F1 & F2
(F1A)

AIR PRESSURE SWITCH CONNECTIONS

SPARK
ELECTRODE

WATER PRESSURE
SWITCH

O/H CUTOFF

CONTROL

STAT

FAN

AIR
PRESSURE
SWITCH

PILOT
SOLENOID

MAIN
SOLENOID

N

N

N

N

N

N

N

(N/O)

(C)

(N/C)

L

K2

K1

N/C

C

N

N

b

w

g

w

br

p

y

y

r

b

r

bk

b

y

br

b

b

bk

b

KEY

bk BLACK
br BROWN
b BLUE
p PURPLE
g GREY

or ORANGE
w WHITE
r RED
y YELLOW

SL

MAIN TERMINAL STRIP CONNECTIONS

CONTROL THERMOSTAT CONNECTIONS

PRINTED CIRCUIT BOARD CONNECTIONS

FULLY PUMPED OPEN VENTED
OR SEALED WATER SYSTEM

PN

9

P

L

PUMP

br

b

br

br

b

b

*

RED

LINK

*

Remove red link between 9 and SL when

fitting a time control etc (if no switch is fitted,
link will make the circulation pump run constantly)

**

LInk fitted to bridge out water pressure switch

for open vented system.

F1

F2

or

or

or

p

**

LINK

Diagram 11.4

11 Fault Finding

Diagram 11.3

Pump overrun Operation for Fully

Pumped System Only

YES

NO

Faulty PCB. Replace

Does pump stop after several minutes ?

YES

Does the pump run when SL is applied ?

Does pump continue to run after SL is interrupted ?

NO

NO

System satisfactory.

YES

The PCB has a pump overrun facility.

The pump should run for several minutes after remote controls have stopped calling for heat.

Before using the fault finding chart ensure all wiring is correct and in good condition, the pump

is not faulty and check the PCB fuse F2.