MAINTENANCE

MAINTENANCE

To ensure the continued efficient and safe operation of the

boiler it is recommended that it is checked and serviced at

regular intervals. The frequency of servicing will depend upon

the particular installation and usage, but in general once a year

should be enough.

It is the Law that any servicing is carried out by a

competent

person approved at the time by the Health and Safety

Executive

.

• Before commencing with a service or replacement of parts

isolate the boiler from the electrical supply and turn off the

gas supply at the gas isolation valve.

• When replacing a part on this appliance, use only spare

parts that you can be assured conform to the safety and

performance specification that we require. Do not use

reconditioned or copy parts that have not been clearly

authorised by Glow-worm.

• If any electrical connections have been disconnected

and after their connection, checks to the earth continuity,

polarity, short circuit and resistance to earth must be

repeated using a suitable multimeter, as described in chapter

"Trouble-shooting ► Fault diagnosis ► Check the electrical

installation".

• After servicing, complete the relevant Service Interval

Record section of the Benchmark Checklist located in the

centre pages of this document.

15 Trouble-shooting

15.1 fault diagnosis

The following checks should be performed before proceeding

onto specific diagnostics:

• Make sure that the electricity supply has not been interrupted

and that the appliance is connected correctly (See chapter

"Trouble-shooting ► Fault diagnosis ► Check the electrical

installation")

• Check the appliance’s gas supply (See chapter "Trouble-

shooting ► Fault diagnosis ► Check the gas supply").

• Ensure that the isolating valves are open.

• Ensure that the pressure indicator displays a value of 0.8 bar

(if the pressure falls below 0.4 bar, the air vent function will

run automatically for a period of 5 minutes until you see 0.5

bar on the pressure indicator). If not, fill the appliance.

• Check that all external controls are connected correctly.

• If the symbol and the message "

rE SEt" are displayed

on the screen, display the fault code memory (see chapter "

Trouble-shooting ►Fault memory").

• Press the reset button to restart the appliance.

• Check the functional flow diagram.

15.1.1

Check the electrical installation

24

V

V

3

2

1

4

Key

1 Main board

2 Neutral

3 Live

4 Multimeter

• Remove the front casing panel

• Check the external electrical supply to the boiler is on and a

supply of 230V is present at the ‘L’ and ‘N’ terminals on the

main board.

• Check the electrical installation and appliance, carry out tests

for earth continuity, polarity, short circuit and resistance to

earth, using a suitable multimeter.

• Bare metal points such as screws or rivets will act as suitable

earth check points on the appliance.

15.1.2

Check the gas supply

1

2

Key

1 Gas service isolation valve

2 Test point

• Check that there is a gas supply to the boiler and the gas

service isolation valve is turned on.

• Check pressure at the gas service isolation valve.