Page 20

Advertising
background image

C-BOX 150

2

2.4.3

Scanner Chassis Grounding Jumper Settings


The scanner chassis grounding method can be selected by positioning a jumper (see
Figure 9). In this way the scanner chassis can be connected to earth ground (only if
pins 7 or 8 are connected to a good earth ground) or to the power supply ground
signal. The scanner chassis can also be left floating but, in this case, the jumper
must be removed.

Figure 9 – Chassis Grounding



2.4.4 Scanner

Selection

DS1100
DS2200

Other Devices


floating

to EARTH
GROUND

(default)

to GND

Figure 10 - Scanner Selection Switch



This switch must be set upward only when a DS1100 or a DS2200 scanner (10-30 V
version) is connected. For all the other devices the switch must be set downward.

12