Pilz PSS SB HYD, Basic license User Manual

Page 113

Advertising
background image

Modular Block System: Hydraulic Presses

6-51

Example 1:
Parameters

ARST, AuST and NFkT = 0

These settings mean that the “start-up disabler” and “reset lock” functions
are activated and a function test of the gate is required.
• With PSS start-up or PSS cold start (start-up disabler), proceed as
follows:

- If the gate is open, close, open and then close the gate again, then

reset via the reset button (

Strt).

- If the gate is closed, open and close the gate and reset via the reset

button (

Strt).

• Subsequent statuses only after enable is issued (reset lock):

- If the gate is open, close the gate and reset via the reset button (

Strt).

- If the gate is closed, reset via the reset button (

Strt).

• If there has been a fault, this must first be rectified before proceeding as

follows:
- If the gate is open, close the gate and reset via the reset button (

Strt).

If error bit 09 occurs (synchronisation time exceeded), close, open and
then close the gate again, then reset via the reset button (

Strt).

- If the gate is closed, open and close the gate and reset via the reset

button (

Strt).

Example 2:
Parameters

ARST and AuST = 0, NFkT = 1

These settings mean that the “start-up disabler” and “reset lock” functions
are activated and a function test of the gate is not required.
• With PSS start-up or PSS cold start (start-up disabler), proceed as
follows:

- If the gate is open, close the gate and reset via the reset button (

Strt).

- If the gate is closed, reset via the reset button (

Strt).

• Subsequent statuses only after enable is issued (reset lock):

- If the gate is open, close the gate and reset via the reset button (

Strt).

- If the gate is closed, reset via the reset button (

Strt).