• Please note:
- With directional control valves (input parameter
VTyp = 0), the reaction
time when the valve switches on and off must always be monitored
(see under “Settings for the parameters
TOn and TOff”).
- With poppet valves, the reaction time when the valve switches on and
off may be monitored (see under “Settings for the parameters
TOn and
TOff”).
Settings for the parameters
TOn and TOff
Poppet valves
I/P Parameter
TOff = 0
0<
TOff<TOff
max
VTyp = 1
TOn = 0
Reaction time is not
Reaction time is monitored
monitored with the valve
when the valve switches
switches on or off
off
0<
TOn<TOn
max
Reaction time is
Reaction time is
monitored when the valve
monitored when the valve
switches on
switches on and off
Directional control valves
I/P Parameter
0<
TOff<TOff
max
VTyp = 0
0<
TOn<TOn
max
Reaction time is monitored when the valve
switches on and off
Setting reaction times
• Select a low value (e.g. 10 ms)
• Increase the value step by step (max. 10 ms steps), until it is clear that
the valve operates safely and correctly.
This will ensure that reaction times correspond to the actual values of the
valve.
SB089
- PSS SB HYD, General license PSS SB HYD, Copy license PSS SB HYD, Update license PSS SB TRA, Basic License PSS SB TRA, General license PSS SB TRA, Copy license PSS SB TRA, Update license PSS SB NOT, Basic license PSS SB NOT, general license PSS SB NOT, Copy license PSS SB NOT, Update license PSS SB FT, Basic license PSS SB FT, General license PSS SB FT, Copy license