Modular Block System: Hydraulic Presses

Temporary flag range in MBS blocks

Internally, MBS blocks use the flags in the range M 64.00 ... M69.31 as
temporary flags.

NOTICE

We recommend the following:

• Do not use flags from the temporary flag range for your own applications.

Malfunctions may occur if you use the temporary flag range M64.00 ...
M69.31 for your own applications.

• If it is absolutely necessary to use this flag range, under no

circumstances should you use the flags:
- in alarm OBs

- as input parameters for standard function blocks

- as output parameters for standard function blocks

- as global parameters

Output parameter FG/ENBL

Many standard function blocks have an enable output FG/ENBL. This
output parameter indicates the enable status of a standard function block.
The enable status results from the standard function block’s check of the
inputs.

FG

/ ENBL = 1:

No error found,
function is enabled

FG

/ ENBL = 0:

An error has been found,
function is not enabled.

INFORMATION
If you are using a Pilz evaluation package we recommend that you use
flags M70.00 ... M88.23 for the output parameter FG/ENBL. You will need
to note the allocation of the flags to the safety subroutine numbers (input
parameter SSNR): SSNR = 1 should use flag M70.00; SSNR = 600 should
use flag M88.23.
The Appendix contains a table showing the allocation of safety subroutine
numbers to enable flags.