Modular Block System: Hydraulic Presses

Safety gate monitoring with automatic start and manual restart,
category 2

Block used: SB066/ST_K4

Cyclical function test on the gate:
The following application requires a cyclical function test of the safety gate
(open/close safety gate).
This requirement is met by carrying out a function test using a 1/0-pulse
edge at the input parameter

MEin.

Set operating mode:
The following operating mode is set for this application:

ARSt = 0: Reset lock activated (manual restart)

The operator must reset each time the safety gate opens
(input parameter

Strt).

NFkT = 1

No function test on safety gate when PSS starts up/resets

AuSt = 1

Automatic start

WARNING!

When a safety-related device provides a start or restart signal, the start or
restart shall take place automatically only if a hazardous situation cannot
exist (EN 954, 03/97).