Error messages, Standard function blocks, Sb087 – Pilz PSS SB HYD, Basic license User Manual

Page 196

Advertising
background image

6-134

Modular Block System: Hydraulic Presses

Standard Function Blocks

Error messages

Any fault that is detected will be stored in the corresponding error data
word (

SSNR) of DB015 (1st data block), until the fault has been fully dealt

with.

• Error messages in DB015

- Bit 01:

Valve acknowledgement input parameter

S remains high after

the valve is switched on.
Remedy: Check switch, cable, input card and all conditions
and then reset (input parameter

RSET)

- Bit 02:

Valve acknowledgement input parameter

S remains low after

the valve is switched off.
Remedy: Check switch, cable, input card and all conditions
and then reset (input parameter

RSET)

INFORMATION
If no reaction time has been set for switching off the valve
(

TOff = 0), Bit 02 will remain set until the valve returns to its

start position. This is not a fault, but is important to bear in
mind.

- Bit 03:

Valve acknowledgement input parameter

S goes to its start

position during operation (input parameter

S goes high while

output parameter

Y = 1)

Remedy: Check switch, cable, input card and all conditions
and then reset (input parameter

RSET)

- Bit 04:

Valve not in its start position (off) when switched on (input
parameter

S • 1)

Remedy: Check switch, cable, input card and all conditions
and then reset (input parameter

RSET)

- Bit 08:

Reset input constantly high, set too early, or

EIN = 1 or S = 0

Remedy: Release reset button and press it again.
If this does not work, check switch, cable, input card and all
conditions and then reset (input parameter

RSET)