Modular Block System: Hydraulic Presses
Standard Function Blocks
Error messages
Any fault that is detected will be stored in the corresponding error data
word (
SSNR) of DB015 (1st data block), until the fault has been fully dealt
with.
• Error messages in DB015
- Bit 01:
Valve acknowledgement input parameter
S remains high after
the valve is switched on.
Remedy: Check switch, cable, input card and all conditions
and then reset (input parameter
RSET)
- Bit 02:
Valve acknowledgement input parameter
S remains low after
the valve is switched off.
Remedy: Check switch, cable, input card and all conditions
and then reset (input parameter
RSET)
INFORMATION
If no reaction time has been set for switching off the valve
(
TOff = 0), Bit 02 will remain set until the valve returns to its
start position. This is not a fault, but is important to bear in
mind.
- Bit 03:
Valve acknowledgement input parameter
S goes to its start
position during operation (input parameter
S goes high while
output parameter
Y = 1)
Remedy: Check switch, cable, input card and all conditions
and then reset (input parameter
RSET)
- Bit 04:
Valve not in its start position (off) when switched on (input
parameter
S • 1)
Remedy: Check switch, cable, input card and all conditions
and then reset (input parameter
RSET)
- Bit 08:
Reset input constantly high, set too early, or
EIN = 1 or S = 0
Remedy: Release reset button and press it again.
If this does not work, check switch, cable, input card and all
conditions and then reset (input parameter
RSET)
SB087