Programmable Outputs

The ST drives feature four digital outputs. These outputs can

be set to automically control a motor brake, to signal a fault

condition, to indicate when the motor is moving or to provide

an output frequency proportional to motor speed (tach signal).

Or the outputs can be turned on and off by program instructions

like Set Output.

The outputs can be used to drive LEDs, relays and the inputs

of other electronic devices like PLCs and counters. For Y4, the

“+” (collector) and “-” (emitter) terminals of each transistor are

available at the connector. This allows you to configure this

output for current sourcing or sinking. The Y1-3 outputs can

only sink current. The Y COM terminal must be tied to power supply (-).

Diagrams of each type of connection follow.
Do not connect the outputs to more than 30VDC.

The current through each output terminal must not exceed 100 mA.

IN/OUT1

YCOM

Y1/2/3

5-24 VDC

Power Supply

+

Load

IN/OUT1

Y1

YCOM

Y3

Y2

14

17

15

16

Y4+

Y4-

20

21

Sinking Output

Using Y4

IN/OUT1

Y4-

Y4+

5-24 VDC

Power Supply

+

Load

Sinking Output

Using Y1, Y2, Y3