4 environmental conditions, Nvironmental, Onditions – CIRCUTOR FRE Series User Manual

Page 17: N table7-4

Advertising
background image

FRE / FRES

17 / 20

- Check that the steps connect and disconnect properly

- Check that there is no consumption in any phase with the step disconnected. If there is

consumption this means that some of the thyristors are defective.

- Check the consumption of the different steps, in each phase. The normal values are shown in

Table7-4

Table 7-4.- Nominal consumption of the LC steps of an FRE or FRES filter

POWER

CURRENT

230V

400V

I

n

I

n

2.5 kvar

6.28 A

3.6 A

5 kvar

12.56 A

7.2 A

7.5 kvar

18.85 A

10.8 A

10 kvar

25.12 A

14.4 A

12.5 kvar

31.41 A

18 A

15 kvar

37.7 A

21.6 A

20 kvar

50.24 A

28.8 A

25 kvar

62.82 A

36 A

30 kvar

75.4 A

43.2 A

40 kvar

100.48 A

57.6 A

50 kvar

125.64 A

72 A

60 kvar

150.8 A

86.4 A

70 kvar

175.92 A

101.1 A

80 kvar

200.96 A

115 A

- Check the voltage on all of the reactor's windings (input - output of the same winding, not

between phases). The voltage depends on the filter's p% factor (see label on the equipment), in

accordance with the following formula:

%)

p

100

(

%

p

.

577

,

0

V

V

)

phase

phase

(

MAINS

L

=

For example, in the case of the 400V grid and p%=7, V

L

=17.38V. For the 400V grid and p%=14,

V

L

=37.57V. For other line voltages, the V

L

value is proportional to the line voltage.

NOTES:

When the consumption of the steps is 25% less than that stated in Table7-4 and the voltage is within

the tolerance limits, this is a sign of degradation in the capacitors. These must be replaced with a

suitable spare part if these symptoms are detected in a step.

When the consumption of the steps is 10% more than the values stated in Table7-4, this can be

caused by the presence of resonances. If this is detected, measure the grid's voltage THD (it must be

under 5%) or check the filter's tuning frequency.

If the voltage drop in a reactor deviates from the values stated in this section, check the reactor. This

phenomenon can be caused by the presence of a resonance.

7.3.3 PF regulator checkings.

Refer to the manual of the specific regulator used in the capacitor bank. This

manual is always supplied with the capacitor bank.

Make sure that there are no damaged segments on the display (abnormal brightness).

Make sure that regulator's keyboard is working properly:

- Enter Setup and check the adjusted values

- Force the manual connection and disconnection of a step.

7.4 Environmental Conditions:

Check that the maximum environmental conditions listed in section 4.3 are observed

Advertising