2 electrical characteristics, 3 environmental characteristics, 4 mechanical characteristics – CIRCUTOR FRE Series User Manual

Page 7: Lectrical characteristics, Nvironmental, Haracteristics, Echanical characteristics

Advertising
background image

FRE / FRES

7 / 20

4.2 Electrical characteristics

- Operating voltage and nominal frequency:

U

n

/ f , listed on the label

- Design voltage:

U

Nn

+ 10% (440 V for 400 V equipment)

- Nominal power and distribution of steps:

Q

n

and composition, (see label)

- Overvoltage factor, p%

Standard 7% ,

Others 14%, 8.2% and 5.67% (see label

)

- Total loss:

Standard 3.5 at 4 W/kvar

- Residual discharge voltage:

75 V after 3 minutes

- Overload capacity:

1.3 . I

n

in all items

- Contact operating voltage:

U

aux

, listed on the label.

NOTE: In general, use a 1.5 mm2 cable to supply external power.

If the label indicates “

Internal” , means that this the auxiliary circuit does not require external power.

- Current Transformer Input:

5 A , (Transformer I

n

/5 A)

NOTE: Minimum cable section 2.5mm2.

- Compliance with Standards

EN-61642 and UNE EN 61921

- Protection elements:

Fuses

Type gL, NH gauge (minimum 1.5 x I

n

)

Reactor thermostat:

90 ºC ±5 ºC

Insulation

3 kV /50 Hz

Breaking capacity

10 A / 250 V

ac

, resistive load

- Capacitor characteristics:

Capacity tolerance:

± 5%

Insulation level from earth:

3 kV /50 Hz

Impulse test:

15 kV , ray type wave 1.2/50 µs

Protection elements:

Internal fuses and over-pressure system

Compliance with Standards

EN 60831

- Reactor characteristics:

Inductor tolerance:

± 5%

Rated voltage

standard 500 V (RMS value)

Saturation current

Standard at 1.4 I

n

, L=5% (

Others for

RBX

)

Level of insulation phases to earth

3 kV /50 Hz; 15kV shockwave 1.2/50 µs

Max. overload Σ(n.I

n

)

2

Permanent 20% ; Transient (1 min) 2 I

n

4.3 Environmental Characteristics

- Capacitor max. temperature

Category C in accordance with EN 60831-1

Maximum for 1h

50 ºC

24h average

40 ºC

Annual average

30 ºC

- Max. temperature of reactors

In accordance with IEC 60076-6

Maximum environmental temperature

60 ºC

Indoor temperature at In

<110 ºC

Protection thermostat

90 ºC

Cabinet ventilation

For Tout > 30 ºC, forced ventilation must

be used for the cabinet

- Maximum relative humidity:

80%

- Altitude:

1000 m (For higher altitudes, always

maintain forced ventilation)

4.4 Mechanical characteristics:

- Protection degree:

Marked on the label:

- Paint

Oven dried epoxy type

- Standard colours

RAL 7035 Grey ; RAL 3005 Maroon

Advertising