2.3 Application warnings

Capacitor banks with detuned filters can attenuate the remote control signals

transmitted through the network which are used in some countries to connect or

disconnect certain loads or lines. When remote control frequencies close to the

tuning frequency of

FRE or FRES filters are used, blocking filters must be placed in

the supply line, or the tuning frequency of the

FRE /or FRES filters must be

changed.

3

RECEPTION, TRANSPORT, HANDLING AND STORAGE

3.1 Reception protocol

Make sure that the equipment has not been damaged during transport.

Check that the equipment received matches with the order and that its electrical characteristics

are suitable for the grid where it is to be connected.

Check the shipping documentation. The dispatch note number must coincide with the number

marked on the outer part of the unit package.

Unload and transport the equipment in accordance with the instructions in section 3.2

Perform an external and internal visual inspection of the equipment prior to connecting it.

Check that all items on the packing list are present and match with the delivered documentation.

If any discrepancy is detected upon reception, immediately contact the transport

company or CIRCUTOR's after-sales services.

3.2 Transport, loading and unloading, handling and storage

The transport, loading and unloading and handling of the equipment must be

carried out with proper precautions and using the proper manual or mechanical

tools to prevent damaging the equipment.
If the equipment is not to be immediately installed, it must be stored at a location

with a firm and level floor and satifying the storage conditions listed in the technical

characteristics section. It is recommended that the equipment be stored with its

original protective packaging.

To move the equipment a short distance, the unit's floor support profiles facilitate handling with a pallet

jack or forklift.

The centre of gravity of some units may be at a considerable height. Therefore,

when handling with a forklift, it is recommended that the equipment be securely

fastened and that no abrupt operations are made. The equipment should not be

lifted more than 20 cm over the ground.

Fig. 3-1 .-Transport with pallet jack

When unloading and moving the equipment, use a forklift with forks long enough to support the entire

length of the base. In the limit, the forks should be long enough to support at least ¾ of the depth. The