Table 4-42, Parameters of cooling system, Using hpi-b – Artesyn System Management Interface Based on HPI-B (Centellis 2000 R3.0/4411) User's Guide (June 2014) User Manual
Page 79
 
Using HPI-B
System Management Interface Based on HPI-B (Centellis 2000 R3.0/4411) User’s Guide (6806800P20C)
79
Reboot the Shelf Manager or restart the HPI daemon with sv_stop and sv_start 
commands in order to activate the modified configuration. Assure that the active Shelf 
Manager works with the modified configuration file.
Table 4-42 Parameters of Cooling System
Parameter Name
Default Value
Description
OPENHPI_LOG_DEBUG_FACILITIES
“”
"ipmicooling" enables logging. It enables 
the shelf manager to log the cooling 
related information into files 
/var/log/bbs-hpib0X.log
where
X
can be in the range of 0 to
OPENHPI_LOGFILE_MAX
as
mentioned in the /etc/bbs-
hpib/bbs-hpib.conf 
configuration
file.
Cooling_DeactOnUpperNonRecov
erTemp
<valid only for C2000 R3.0 systems>
“1”
Enables the function to power off all 
blades and drop fan speed after 
receiving upper non recoverable (UNR) 
thermal events from two different 
resources in the C2000 R3.0 shelf.
Cooling_FanMinimumLevel
“12|15”
Default fan speed in %.
12 - default value for C2000 R3.0 shelfs.
15 - default value for the other shelfs.
Cooling_InletOutletLowerTemp
erature
“20”
Lower temperature point for inlet/outlet 
control
Cooling_InletOutletUpperTemp
erature
“40”
Upper temperature point
Cooling_InletOutletLowerSetP
oint
“10”
Set point at upper temperature
Cooling_InletOutletUpperSetP
oint
“25”
Set point at lower temperature Range 25 
to 15, most effect at 15. Influences the 
difference between in- and outlet 
temperature.
Cooling_InltOutltMinimumSens
orTemperature
“18”
Below this inlet temperature the 
inlet/outlet related control is disabled