9171300990 Rev V

Table 1-1. Multiples of Tap

Front Panel Setting %

15

20

25

30

35

40

45

50

55

60

Maximum Restraint

Current At Minimum

Pickup In Multiples of

Tap

2.33 1.75 1.40 1.17 1.00 0.875 0.778 0.700 0.636 0.583

Figure 1-2. Percentage Restraint Characteristic

Second-Harmonic Restraint Inhibit of the restrained output occurs when the second-

harmonic component exceeds a pickup setting which is 12%

of the operating current for single-phase units or 18% for

three-phase units.

Fifth-Harmonic Restraint

Inhibit of the restrained output occurs when the fifth-harmonic

component exceeds a pickup setting which is 35% of the

operating current.

Unrestrained Output

Pickup Range

Front panel thumbwheel switches adjust the pickup point of

the unrestrained output over a range of 6 to 21 times the tap

setting in increments of 1 x Tap.

Pickup Accuracy

±

3% of the front panel setting.