General, Description, Current transformers – Basler Electric BE1-87T User Manual

Page 35: Scaling, Summing, 30° internal phase shift (three-phase relays only), Section 3 • functional description -1, General -1, Description -1, Current transformers -1

Advertising
background image

9171300990 Rev V

BE1-87T Functional Description

3-1

SECTION 3 • FUNCTIONAL DESCRIPTION

General

BE1-87T relays are solid-state devices that protect transformers by providing output contact closure when

the scaled current into the protected transformer does not equal the scaled current out, within defined

limits. These relays are harmonically restrained to prevent tripping during initial energization and external

fault conditions. A through-current restraint also provides security against tripping for external faults. An

unrestrained tripping element is included to provide a high-speed trip in the event of a particularly severe

fault within the transformer.

Description

The functional block diagrams of Figures 3-1 and 3-2 illustrate the overall operation of the BE1-87T

Transformer Differential Relay. (Figure 3-1 shows Phase A or single-phase functions; Figure 3-2 shows

the additional functions for phases B and C.) Since the three phases are functionally similar, only phase A

is shown in detail in Figure 3-1. Note that in a three-phase unit, there may be one restrained output for

each phase (Output Type Option E in the third position of the Style Number), or one restrained output that

serves for all three phases (Option F in the third position). When Target Option C or D is specified for a

three-phase Unit (in the seventh position), an individual target is supplied for each phase.

Current Transformers

In the protected zone of the power system, CTs with a 1 ampere or 5 ampere secondary winding supply

the sensing current for each input. This is not

Scaling

shown in Figure 3-1 or Figure 3-2. Other relays may be

connected ahead of the BE1-87T. Sensing currents are, in turn, applied to relay internal input

transformers. These transformers provide system isolation.

Input currents are scaled by the front panel

INPUT rotary switches that introduce resistances to the

internal CT secondaries. The switches are calibrated in 0.02 ampere increments from 0.4 to 1.78 ampere

for 1 ampere CT units (Options 2 or 4 in the second position of the Style Number), and in 0.1 ampere

increments from 2.0 to 8.9 amperes for 5 ampere CT models (Options 1 or 3 in the second). The many

graduations of adjustment are provided to allow each input to approach an ideal representation of the

actual operating per unit value.

Summing

Analog signals representing each input contribution are vector summed (shown as Summing in Figure 3-

1). This summing process produces the operating current (I

OP

) that is the phasor sum of the input

currents.
Ideally, and with perfectly matched CTs, a transformer without an internal fault should cause I

OP

to be

exactly zero on a continuous basis. When not zero, a fault would be indicated. However, saturation effects

caused by heavy through-current or magnetic inrush can cause a temporary imbalance even though no

internal fault has occurred. To prevent a false trip under such conditions, various types of restraint are

used. Each restraint is specific to a potential cause of misoperation. These are individually discussed in

the topic Restrained Trip Output.

30° Internal Phase Shift (Three-Phase Relays ONLY)

For three-phase units, the inputs to the Summing function are first routed through the 30° Phase Shift

circuit. There the signals may be advanced or retarded by 30° or passed through unchanged.

Compensating phase shift direction (shown as the Phase Shift Setting circuit in Figure 3-1) is determined

by the position of three jumpers on the internal Analog #2 Board. (The location of these jumpers is shown

in Figure 2-4.) The internal phase shift will accomplish the corresponding zero sequence blocking. The

current magnitude will be increased by

3

and must be taken into account in the tap setting (explained

later in detail in Section 4).

Advertising