BE1-87T Installation

9171300990 Rev V

Step 2. Withdraw the cradle assembly (see Figure 4-19).

Step 3. Remove the four screws that attach the front panel to the cradle assembly, and remove the

front panel.

Step 4. With a slight side-to-side rocking motion, withdraw Analog Board #1.

Figure 4-20. Side View of Cradle Assembly

Disabling Unused Inputs

To eliminate the possibility of a spurious input from induced currents within the relay, special internal

jumpers have been provided to disable any inputs that are not connected to CT wires.

CAUTION

Disabling unused inputs requires disassembly of the relay and must be done

when the relay has been taken out of service. Access to the input-disabling

jumpers requires the removal of the Analog #1 Board, shown in Figure 4-19.

To avoid personal injury or equipment damage, do

NOT proceed unless

thoroughly familiar with the instructions in sections Relay Operating

Precautions and Relay Disassembly: Precautions.


MOTHERBOARD

FRONT

PANEL

FRONT

PANEL

MOTHERBOARD

SINGLE-PHASE

THREE-PHASE

ANALOG BOARD #1

POWER SUPPLY

POWER SUPPLY

ANALOG BOARD #2

ANALOG BOARD #1

ANALOG BOARD #1

ANALOG BOARD #1

ANALOG BOARD #2

UPPER SWITCH BOARD

LOWER SWITCH BOARD

UPPER SWITCH BOARD

LOWER SWITCH BOARD

D638-003

2-23-93

BE1-87T

0 A

0 B

0 C