Location of controls and indicators, Section 2 • controls and indicators -1, Location of controls and indicators -1 – Basler Electric BE1-87T User Manual

Page 25: Table 2-1. controls and indicators

Advertising
background image

9171300990 Rev V

BE1-87T Controls and Indicators

2-1

SECTION 2 • CONTROLS AND INDICATORS

Location of Controls and Indicators

Table 2-1 lists and briefly describes the operator controls and indicators of the BE1-87T Transformer

Differential Relay. Reference the call-out letters A through M to Figures 2-1 to 2-3; N through Q to Figure

2-5. Exploded views of controls that are mounted inside the relay (call-out letters B, D and I) are shown in

Figure 2-4.

Table 2-1. Controls and Indicators

Letter

Control or Indicator

Function

A

INPUT

(or TAP) Switches

Front panel

INPUT switches are used to scale the

transformer currents. There are two of these rotary

switches for each input.

1 Ampere CT Units

Each of the upper switches is calibrated to represent

the tenths and units digits (0

.4 through 1.6) of tap

value. Each of the lower switches is calibrated to

represent two-hundredths of tap value for each

increment. Always add the setting of the lower switch to

that of the upper switch. For example, if a setting of

1

.02 is desired, the upper switch must be at 1.0 and the

lower switch must be at 0

.02. The total setting range for

each input is 0

.4 to 1.78.

5 Ampere CT Units

Each of the upper switches is calibrated to represent

the units digit (2 through 8) of tap value. Each of the

lower switches is calibrated to represent tenths of tap

value. Always add the setting of the lower switch to that

of the upper switch. For example, if a setting of 5.0 is

desired, the upper switch is set to 5

.0, the lower switch

must be at 0

.0. The total setting range for each input is

2

.0 to 8.9.

B

30° Phase Shift Jumpers

(three-phase units ONLY)

These jumpers control the internal phase shift of the

relay, either +30°, -30°, or 0°, depending upon the

position of the jumpers provided for each input on the

Analog #2 Board, shown in Figure 2-4. Additional

information is in Section 4.

C

UNRESTRAINED PICKUP

LEVEL

Switches

This thumbwheel switch establishes the desired pickup

setting for all phases of the unrestrained output. The

adjustment range is from 6 to 21 times the phase tap

setting, in increments of 1.

D

CALIBRATE Switch

(three-phase units ONLY)

A two-position switch is located on each Analog #1

Board and is easily accessible on the right side of the

relay when it is withdrawn from the case. In the

CALIBRATE position, these switches inhibit the

harmonic share feature when calibrating the 2nd

Harmonic Restraint. In the

NORMAL position, the relay

will operate normally.

E

POWER

Indicator

This LED will illuminate when operating power is

supplied to the internal circuitry of the relay.