BE1-87T Installation

9171300990 Rev V

Procedure Two

Refer to Figure 4-37 for a one-line drawing of this example.

Data

Figure 4-38. Two Winding Transformer Relay Setting Calculation Example

Specifications

High side

Low side

kV

69

12.47

MVA

12/20

12/20

CT Ratio

600

1200

CT Tap

300

800

CT Accuracy Class

400

800

CT Resistance (ohms)

0.18

0.48

One-Way Lead Burden

(ohms)

0.7

0.7

XFMR Connection*

DELTA

WYE

CT Connection

WYE

WYE

Input #

1

2

Fault Current (Three-

Phase)

1,916

10,603

Fault Current (Single-

Phase)

1,171

11,231

*

Standard connection: High voltage leads low voltage by 30°.

Step 1. Determine the full load primary current (I

P

) of each winding:

Tap and Phase Shift Settings

Use the top kVA rating of the transformer when making the calculations:

HIGH

LOW

IP =

×

MVA rating of transformer

1,000

V

3

LINE - LINE

(

)(

)

(

)

(

)

IP
IP

=

=

20,000

69

167.35

3

I

I

P

P

=

=

20,000

12

3

925

.47

.98