Figure 3-1. functional block diagram – Basler Electric BE1-87T User Manual

Page 36

Advertising
background image

3-2

BE1-87T Functional Description

9171300990 Rev V

Figure 3-1. Functional Block Diagram

NOTES

1 Present in three-phase units ONLY.

2 Inputs 4 and 5 are available in single-phase units ONLY.

3 The settings are calibrated to a specified percentage of the harmonic to the fundamental. See

Harmonic

Restraints for factory settings.

4 Phase Targets are supplied on three-phase units ONLY.

5 Restrained Trip Contact:

One contact for single-phase units.

One contact or one contact per phase available on three-phase units.

6 Three-phase units use the sum of the second harmonic from each phase to restrain each phase.
7 Phase Targets are supplied on three-phase units ONLY.
8 Restrained Trip Contact:

One contact for single-phase units.

One contact or one contact per phase available on three-phase units.

Figure 3-2. Functional Block Diagram, Phase B and Phase C

B

C

4

RESTRAINED

UNRESTRAINED

RESTRAINED

UNRESTRAINED

TARGET

TARGET

B SAME AS A

0

0

OR

OR

B

0

C

0

C SAME AS A

0

0

0

0

OPTIONAL

RESTRAINED

CONTACTS

FOR EACH OF

3 PHASES

(SEE NOTE 5

BE1-87T

D741-001b

7-11-94

COM.

IN. 1

IN. 2

IN. 3

COM.

IN. 1

IN. 2

IN. 3

0B

0 C

S2

S1

IN. 3, B SCALE

IN. 3, C SCALE

0

0

IN. 1, B SCALE

IN. 1, C SCALE

0

0

OPERATING

POWER

POWER

SUPPLY

POWER

SUPPLY

STATUS

5

REST.

TRIP

AUX.

OPTION

UNREST

TRIP

TARGET

UNRESTRAINED

B

RESTRAINED

6

POWER

TO INTERNAL

CIRCUITRY

Iop

1

SHIFT SETTING:

+30°, -30°, 0°

8

LEDs

CALCULATE

MAXIMUM

INDIVIDUAL

CURRENT

THEN TRIP

op

I

IF

>% max

I

% OF

TRIP

UNREST. SETTING

COM.

IN. 1

IN. 2

IN. 3

IN. 4

IN. 5

TO OTHER PHASES

(THREE-PHASE ONLY)

UNREST

TRIP

(6 TO 21

TIMES TAP)

2

0

30 °

SHIFT

(ONLY ON

3 UNITS)

0

0

SCALING

( TAP)

SCALING

( TAP)

SCALING

( TAP)

IN. 2, B SCALE

IN. 2, C SCALE

0

0

SCALING

( TAP)

0

C

0

5TH >

SETTING

=INHIBIT

3

2ND >

SETTING

=INHIBIT

3

OR

B
C

0
0

4

TARGET

TARGET

SCALING

( TAP)

POWER

SUPPLY

SENSOR

FIFTH

HARMONIC

RESTRAINT

FILTERS

SECOND

HARMONIC

RESTRAINT

FILTERS

SUMMING:

ALGEBRAIC

SUM OF

INPUTS =

OPERATING

CURRENT

( )

Iop

OR

30 °

SHIFT

(ONLY ON

3 UNITS)

0

0

30 °

SHIFT

(ONLY ON

3 UNITS)

0

0

2

max

I

% I max

REST.

T

PICKUP

CONTROL

% Imax

op

I

UNREST.

SETTING

THEN TRIP

IF I >

op

A

OR

1 0

0

BE1-87T

D741-001a

7-11-94