BE1-87T General Information

1-7

Outputs

Output contacts are rated as follows.

Resistive

120/240 Vac

Make 30 A for 0.2 seconds, carry 7 A continuously and break

7 A.

250 Vdc

Make and carry 30 A for 0.2 seconds, carry 7 A continuously

and break 0.3 A.

500 Vdc

Make and carry 15 A for 0.2 seconds, carry 7 A continuously

and break 0.1 A.

Inductive

120/240 Vac, 125/250 Vdc

Make and carry 30 A for 0.2 seconds, carry 7 A continuously

and break 0.3 A, (L/R = 0.04).

Target Indicators

Target indicators may be either internally-operated or current-

operated (operated by a minimum of 0.2 A through the output

trip circuit). When the target is current-operated, the

associated output circuit must be limited to 30 A for 0.2

seconds, 7 A for 2 minutes and 3 A continuously.

Single-Phase Units

Either an internally-operated or a current-operated target is

supplied (as selected by the Style Number) for each trip

output (i.e., the restrained and the unrestrained functions).

Three-Phase Units

Either internally operated or current operated targets (as

selected) indicate the function (restrained or unrestrained)

that caused the trip, and the tripped phase (A, B, C).

Harmonic Attenuation

Refer to Table 1-2.

Table 1-2. Harmonic Attenuation

Parameter

(50 Or 60 Hz Models)

Minimum Attenuation at Indicated Fundamental

50/60 Hz 100/120 Hz 150/180 Hz 250/300 Hz 500 Hz

Through Current

0

0

0

0

12 dB

Operating Current

0

0

0

0

12 dB

2nd Harmonic Restraint

12 dB

0

12 dB

12 dB

12 dB

5th Harmonic Restraint

12 dB

12 dB

12 dB

0

12 dB