Instantaneous (unrestraint) unit setting – Basler Electric BE1-87T User Manual

Page 88

Advertising
background image

4-46

BE1-87T Installation

9171300990 Rev V

Neglecting R

R

, use R

W

and R

L

from Figure 4-37:

HIGH*

LOW

V

BG

=
=

19.5(0.7)

13.6 V

VBG

=
=

70 (2(0.7))
98.0 V

NOTE

Since a phase-to-ground fault looks like a phase-to-phase fault on the delta

side of a delta/wye transformer, each CT only has to carry one times the one

way lead burden.

Step 15. Determine the effective CT accuracy class (V

CE

):

HIGH

LOW

Step 16. Determine the saturation factor (S

F

):

VB is the largest of the burden voltages calculated in steps 13 and 14.

HIGH

LOW

11

.

0

200

4

.

22

=

=

F

S

18

.

0

3

.

533

0

.

98

=

=

F

S

NOTE

Maximum Recommended SF = 0.5.


Larger saturation factors will make the relay insecure for external faults. The only solution is to increase

the CT quality.

Step 17. Determine the maximum external fault multiple (I

E

).

Instantaneous (Unrestraint) Unit Setting

For wye-connected CTs and with WYE jumpers on Analog Board #2, shown in Figure 2-

4:

I

I

T

E

F

=

=

Maximum Relay Fault Current

Corresponding Tap

V

V

N

N

CE

C

A

=

=

(Base Accuracy) (Number of CT Turns in Use)

Maximum Ratio

( )

V

CE

=
=

(400) 300

600

200

V

CE

=

=

800 800

2000

5333

(

)

.

S

F

V

B

V

CE

=

Advertising