Dielectric test, Connections, Dielectric test -9 – Basler Electric BE1-87T User Manual

Page 51: Connections -9, Figure 4-8. case terminals: single-phase

Advertising
background image

9171300990 Rev V

BE1-87T Installation

4-9

Dielectric Test

In accordance with IEC 255-5 and ANSI/IEEE C37.90-1989, one minute dielectric (high potential) tests

may be performed as follows.

All circuits to ground: 2,121 Vdc

Input to output circuits 1,500 Vac or 2,121 Vdc

Note that this device employs decoupling capacitors to ground at all the output terminals, and at the

power supply terminals (3, 4). Accordingly, a leakage current of approximately 15 milliamperes per 1000

Vac is to be expected.

Connections

Incorrect wiring may result in damage to the relay. Be sure to check the model and Style Number against

the options listed in the Style Number Identification Chart (Figure 1-1) before connecting and energizing a

particular relay.

NOTE

Be sure the relay case is hard-wired to earth ground with no smaller than 12

AWG copper wire attached to the ground terminal on the rear of the relay

case. When the relay is configured in a system with other protective devices, it

is recommended to use a separate lead to the ground bus from each relay.


Except as noted above, connections should be made with a minimum wire size of 14 AWG. Figures 4-7

through 4-10 show case terminals designations for four typical relay configurations. Figures 4-11 through

4-14 show the internal connections of the BE1-87T. Control circuit connections are shown in Figures 4-15

through 4-18.

CAUTION

To prevent possible false tripping, the upper connection plug should be in

place prior to removing or installing the lower connection plug.

Figure 4-8. Case Terminals: Single-Phase

Advertising