Flowserve Worthington WXB User Manual

Page 23

Advertising
background image

WXB USER INSTRUCTIONS ENGLISH - 07/14

Page 23 of 51

5.2.13 Lubrication

The bearing housing shall be filled with proper
lubricating oil prior to start up. If the pump will be
started after a longer storage period, the bearing
housing should be first flushed and cleaned with
gasoline. It is not necessary to remove the
preservation oil as this will mix up thoroughly with the
lubrication oil.
Lubrication is provided by the pumping effect of the
rotating ball bearings. Maintaining the correct oil level
(middle of the oil sight glass) ensures that the lower
ball bearing is covered with oil.
For recommended lubricating oils refer to the
lubrication table 5.2.6

5.2.14 Oil change

After first start up, the oil shall be changed after 200
service hours.
Every further oil change shall take place after about
2000 service hours or at least every 6 month.
To change the oil, use the following procedure:
a) Remove the reservoir (for some type of oilers you

must loose a fixing screw or lock nut, refer to section
5.2.3 Oil level).

b) Open the oil drain on the bearing housing to remove

the oil.

c) Close the oil drain and fill in Oil through the oiler until

the oil level reaches the bottom of the sight glass.

d) Fill the reservoir and put it quickly to the body of the

oiler. Observe the level in the reservoir. It will
decrease until the required oil level is reached
(middle of the sight glass). Ensure that enough oil
remains in the reservoir.

e) If necessary, the oil level can be adjusted by refering

to section 5.2.3 Oil level.

5.2.15 Oil level

The correct oil level is in the middle of the oil sight glass
and shall be checked when pump is not in operation.
Periodically check if the lubricating oil is mixed with any
condensed water. Careful opening of the oil drain
during a stop of the pump will show any water.

Use a spirit level to check the horizontal

alignment of the bearing housing.

A too high oil level will result in higher bearing

temperatures and therefore poorer lubrication.

5.2.15.1 Adjusting of TRICO Constant Level Oiler

If the pump is fitted with a Constant Level Oiler type
„TRICO“, the correct oil level has to be checked after
fitting the pump! Dimension a is the distance from the
centerline of the pump to the minimum oil level (marks
at the bearing housing).

1

Trico-Oiler

2

fixing screw

3

leveling screw

4

oil sight glass

5

oil drain

6

counter nut


a) To check quickly the correct oiler adjustment,

measure the dimension x from the oiler-rim to the
minimum oil level (lower mark at the bearing
housing). After that check the dimension from the
oiler rim to the adjusting screw and compare it
with the dimension x, if required turn the adjusting
nut with tolerances of plus 0 mm and minus 2 mm
(see figure), and fix it.

b) Additionally you can check the correct oiler

adjustment by an oil sight glass (minimum oil
level is the middle of the oil sight glass).


Advertising
This manual is related to the following products: