WXB USER INSTRUCTIONS ENGLISH - 07/14

Page 5 of 51

run-up process (See section 5 Commissioning,
startup,
operation and shutdown).

NEVER RUN THE PUMP DRY

BALANCE LINE MUST BE

OPEN AT ANY TIME. (Except maintenance work)

INLET VALVES TO BE FULLY

OPEN WHEN PUMP IS RUNNING
Running the pump at zero flow or below the
recommended minimum flow continuously will cause
damage to the seal.

DO NOT RUN THE PUMP AT

ABNORMALLY HIGH OR LOW FLOW RATES
Operating at a flow rate higher than normal or at a
flow rate with no back pressure on the pump may
overload the motor and cause cavitation. Low flow
rates may cause a reduction in

pump/bearing life,

overheating of the pump, instability and
cavitation/vibration.

When ambient temperatures are

likely to drop below freezing point, the pump and any
cooling and flushing arrangements must be drained
or otherwise protected.

HANDLING COMPONENTS

Many precision parts have sharp corners and the
wearing of appropriate safety gloves and equipment
is required when handling these components. To lift
heavy pieces above 25 kg (55 lbs) use a crane
corresponding to the mass and in accordance with
current local regulations.

NEVER DO MAINTENANCE WORK WHILST THE
UNIT IS CONNECTED TO POWER

HAZARDOUS LIQUIDS

When the pump is handling hazardous liquids care
must be taken to avoid exposure to the liquid by
appropriate sitting of the pump, limiting personnel
access and by operator training. If the liquid is
flammable and/or explosive strict safety procedures
must be applied.
Gland Packing must not be used when pumping
hazardous liquids.

DRAIN PUMP AND ISOLATE PIPEWORK

BEFORE DISMANTLING THE PUMP
The appropriate safety precautions should be taken
where the pumped liquids are hazardous.

FLUORO-ELASTOMERS (When fitted)

When a pump has experienced temperatures over
250 °C (482 ºF), partial decomposition of fluoro-
elastomers (example: Viton) will occur. In this
condition these are extremely dangerous and skin
contact must be avoided.

GUARDS MUST NOT BE REMOVED WHILE

PUMP IS OPERATIONAL

THERMAL SHOCK

Rapid changes in the temperature of the liquid within
the pump can cause thermal shock, which can result
in damage or breakage of components and should be
avoided.

NEVER APPLY HEAT TO REMOVE

IMPELLER
Trapped lubricant or vapour could cause an
explosion.

HOT AND COLD PARTS

If hot or freezing components or auxiliary heating
supplies can present a danger to operators, they
must

be shielded to avoid accidental contact. If

complete protection is not possible, the machine
access must be limited to maintenance staff only.
Note: bearing housings must not be insulated and
drive motors and bearings may be hot.
If the temperature is greater than 68 °C (155 °F) o r
below 5 °C (41 °F) in a restricted zone, or exceeds
local regulations, action as above shall be taken.

1.6.4 Products used in potentially explosive
atmospheres

Measures are required to:

Avoid excess temperature

Prevent build up of explosive mixtures

Prevent the generation of sparks

Prevent leakages

Maintain the pump to avoid hazard


The following instructions for pumps and pump units
when installed in potentially explosive atmospheres
must be followed to help ensure explosion protection.
Both electrical and non-electrical equipment must
meet the requirements of European Directive
94/9/EC.

1.6.4.1 Scope of compliance

Use equipment only in the zone for which it is

appropriate. Always check that the driver, drive
coupling assembly, seal and pump equipment are
suitably rated and/or certified for the classification of
the specific atmosphere in which they are to be
installed.