7. Connect the electric current and

check this setting as follows:
a. Run the valve to mid-position by

hand.

b. Press the “open” pushbutton -

make sure moving the valve is in
the “open” direction.

c. Allow the limit switch to stop the

motor.

d. After the motor has stopped, turn

the valve by hand to make sure
their is sufficient clearance
between the valve backseat and
the position at which the valve
stem comes to rest.

8. To set the position for operation of

the indicating light, make sure the
torque switch is properly wired into
the closing circuit (see procedure for
setting torque switch below
), and run
the valve to the closed position. Back
the valve off the seat to the desired
position and set the “closed” light

contact using the same procedure
outlined under steps 4, 5a, 5b, and
6, but use the intermittent gear shaft
for the light contacts.

9. When the settings are complete, the

setting rod should remain in the posi-
tion described in step 6.

Torque Switch

See Illustration No. 19.
The procedure for setting the torque switch,
both single and double, is as follows:

Single Torque Switch

1. Make sure the electric current is off.
2. Loosen the jam nut (F).
3. Move the socket head adjusting

screw (G) in for light seating.

4. Close the valve by the motor and

test for tightness of closing. If the
valve closes tightly enough, tighten
the jam nut.

5. For heavier seating move the adjust-

ing screw (G) out and re-tighten the
jam nut.

6. The threaded bushing (E) is intended

to limit the maximum setting of this
torque switch and is locked in posi-
tion to limit the output torque to the
maximum safe rating for the unit.

Double Torque Switch

1. Make sure the electric current is off.
2. Loosen the jam nut (F). Note: The

right side of this switch (K) normally
limits the torque applied in closing
the valve. There are cases of special
valve assemblies where the right side
of this switch limits the torque in the
open direction. In all cases it is
recommended that this be checked
upon installation.