User Instructions - Digital Positioner 3200MD LGENIM0059-09 12/13

5

Table VII: Hazardous Area Certifi cations

North America (FM/CSA)

Flame Proof

SIRA 03ATEX1387

II 2 GD

Ex d IIB+H2 T5 IP65

Ex tD A21 IP65 T95˚C (Ta =-40°C to +80°C)

T5 (Ta = -40˚C to +80C

Explosion Proof

Class I, Div 1, Groups B,C,D

DIP Class II, III, Div 1 Groups E,F,G

Class I, Zone 1, Ex d IIB+H2 (CSA Only)

T5 Tamb = -40˚C ≤ Ta ≤ +80˚C (CSA Only)

T6 Tamb = -40˚C ≤ Ta ≤ +60˚C

Type 4X

Intrinsically Safe

SIRA 03ATEX2299X

II 1 GD

Ex ia IIC Ex iaD 20 T95˚C

T4 (Ta = -52˚C to +85˚C) (Ta = -52˚C to +80˚C)

T5 (Ta = -52˚C to +55˚C)

Entity Parameters

Ui = 30V

Ii = 100mA

Pi = 800mW

Ci = 30nF Co = 36nF

Li = 0

Intrinsically Safe

Class I,II, III, Div 1, Groups A,B,C,D,E,F,G

Class I, Zone 0, AExia IIC (FM Only)

T4 Tamb = -50˚C ≤ Ta ≤ +85˚C

T5 Tamb = -50˚C ≤ Ta ≤ +55˚C

Type 4X

Entity Parameters

Ui = 30V

Ii = 100mA

Pi = 800mW

Ci = 30nF

Li = 0

Non-Incendive

SIRA 08ATEX4006

II 3 GD

Ex nL nA IIC

Ex tD A22 T95˚C (Ta = -52°C to +80°C)

T4 (Ta = -52˚C to +85˚C)

T5 (Ta = -52˚C to +55˚C)

Non-Incendive

Class I, Div 2, Groups A,B,C,D

T4 Tamb = -50˚C ≤ Ta ≤ +85˚C

T5 Tamb = -50˚C ≤ Ta ≤ +55˚C

Type 4X

Barriers Not Required

IECEx

InMetro

Explosion Proof

IECEx SIR 04.0023X

Ex d IIB+H2 T5

Ta = -40˚C to +55˚C

Explosion Proof

TÜV 11.0070

Ex d IIB+H2 T5 Gb IP65

Ta = -40˚C -Ta - +80˚C

Intrinsically Safe

IECEx FMG 05.0003X

Ex ia IIC Ex iaD 20 T95˚C

T4 Ta = -40˚C to +85˚C Ta = -40C to +80˚C

T5 Ta = -40˚C to +55˚C

Entity Parameters

Ui = 30V

Ii = 100mA

Pi = 800mW

Ci = 30nF

Li = 0

Instrinsically Safe

TÜV 11.0071X

Ex ia IIC Ga IP65 Ex ia IIIC T95˚C Da IP65

T4 Ta = -40˚C-Ta- +85˚C Ta = -40˚C-Ta- +85˚C

T5 Ta = -40˚C-Ta- +55˚C

Entity Parameters

Ui = 30Vcc

Ii = 100mA

Pi= 800mW

Ci = 30nF

Li = 0

KOSHA

Gost

Explosion Proof

10-AV4BO-0560X

Ex d IIB+H2 T5

T5 Ta = -20°C to +50°C

Special Conditions for Safe Use:

•

The equipment must be installed in such a manner as to minimize the risk of impact or friction with other metal surfaces.

•

To avoid possibility of static discharge clean only with a damp Cloth

•

In order to maintain the explosion proof certifi cations do not remove or loosen covers while circuits are live.

•

For Intrinsically Safe installations the positioner must be connected to suitably rated intrinsically safe equipment, and must be installed in accordance

with intrinsically safe installation standards.
•

Substitution of components may impair Intrinsic Safety.