Figure 1: shielded wire diagram, Wiring and grounding guidelines, Installation valve installation – Flowserve 2000 Series Digital Positioner User Manual

Page 2

Advertising
background image

42-2

Flowserve Corporation, Valtek Control Products, Tel. USA 801 489 8611

DCS

+ Analog Input

- Analog Input

+ Analog Output

- Analog Output

+ RS485

- RS485

+ 24V

- 24V

StarPac II User Interface Terminal

Grounding Screw for

Electrical Ground of Conduit

No Shield Connection at

StarPac II User Interface Terminal

Shields

Instrument

Ground

Shields

Instrument

Ground

AIB, Extender or

RS232/RS485 Converter

Figure 1: Shielded Wire Diagram

Preferred StarPac II / Logix 2000 Grounding

Tools required for StarPac II / Logix 2000

Maintenance and Start-up

1. Multi-meter w/alligator clips, probes & jumpers
2. 4-20 mA analog calibrator with power supply
3. RS-232-485 communication and cabling
4. Windows

TM

compatible PC

5. Standard 6-inch flat screwdriver
6. Standard phillips screwdriver
7.

1

/

4

-inch flat screwdriver

8. Small wire cutter (flush cut) & wire strippers
9. Needle-nose pliers

10.

1

/

16

-inch allen wrench

11. Vise grips
12. Small vise grips
13.

1

/

2

-inch nut driver

14.

5

/

32

-inch allen wrench

15. Large crescent wrench (minimum 15-inch)
16. 8-inch channel lock pliers
17.

3

/

32

-inch screwdriver

18. Wrist grounding strap
19. Antistatic bag or packaging
20. EPROM remover (PLCC type)
21. Electrical tape
22. Feedback shaft tool and drive module

pressure calibration connectors (supplied
with feedback module kit)

If the StarPac II is being installed in an insulated process
line, do not place more than four inches of insulation
around the pressure or temperature sensors; otherwise
the sensors may not operate properly. In addition,
NEVER insulate the unit electronics assembly or
remote-mounted temperature/pressure sensors (when
used).

CAUTION: Do not insulate the StarPac II / Logix
2000 electronics housing or remote-mounted pres-
sure or temperature sensors; otherwise excessive
heat may build up and affect operation.

Wiring and Grounding Guidelines

This section will help you achieve a maximum “noise -free”
environment and performance with a StarPac II / Logix
2000 unit.

Shielding Versus Grounding

All signals to the StarPac II / Logix 2000 unit should be
in shielded cables. Shields must be tied to a ground at
only one end of the cable to provide a place for environ-
mental electrical noise to be removed from the cable. A
ground wire (unlike a shield) is attached at both ends to
provide a continuous path for electrical conductivity.

Grounding Screw

The green grounding screw by the user interface termi-
nal block should be used to provide the unit with an
adequate and reliable earth ground reference. This
ground should be tied to the same ground as the
electrical conduit. Additionally, the electrical conduit
connecting to the unit should be earth grounded at both
ends of its run.

The green grounding screw must not be

used to terminate signal shield wires.

24VDC Power

The 24 VDC connection points will work best with
shielded twisted pair wire with the shield wire connected

INSTALLATION

Valve Installation

The StarPac II / Logix 2000 Intelligent Control System
valve is installed in the same manner as a conventional
control valve and according to industry standards. Refer
to the appropriate valve installation, operation, mainte-
nance instructions for proper installation procedures.

Advertising
This manual is related to the following products: