9 maintenance, 10 spare parts, 11 troubleshooting – Flowserve F39 Series Pneumatic Actuator User Manual

Page 8

Advertising
background image

8

®

Series F39 Pneumatic Actuator - WCENIM2036-00 05/15

9 MAINTENANCE

CAUTION: The actuator must be isolated both pneumat-

ically and electrically before any maintenance activity is
begun.

Periodic checks should be performed to make certain
that all fasteners remain tight.

All actuators are supplied with sufficient lubrication for
their normal working life. If required, recommended lubri-
cation for all standard actuators is a #1 grease. Consult
Flowserve for lubricants used for high or low temperature
applications.

Depending upon the conditions under which the actu-
ator must work, such as extended duty, non-compatible
operating media or abnormal operating conditions,
periodic replacement of internal seals is recommended.
Repair kits containing all necessary seals can be obtained
through any authorized Worcester/McCANNA distributor.

On spring-return actuators, the springs may need replace-
ment after extended duty since springs may fatigue and
break. SPRINGS SHOULD ALWAYS BE REPLACED IN
COMPLETE SETS. Spring kits are available through any
authorized Worcester/McCANNA distributor.

10 SPARE PARTS

The following are recommended spare parts which should
be kept on hand for Series F39 pneumatic actuators:

Repair Kit(s) – Kits contain all necessary seals, bearings
and instructions.

Spring Kit(s) – For Spring-Return Actuators.

11 TROUBLESHOOTING

WARNING:

BEFORE DISASSEMBLING ACTUATOR FOR

ANY REASON, CONSULT REBUILDING INSTRUCTIONS
CONTAINED IN FOLLOWING SECTION.

For solenoid controlled actuators (with Worcester/
McCANNA solenoid control block)

11.1

If actuator does not function, check to ascertain:

11.1.1 That valve is free to rotate. This can be done as described

above in Manual Operation (Section 8.4).

11.1.2 That actuator is the correct size.

11.1 3 That speed control screws are loose (if screws are tight-

ened all the way, actuator will not operate).

11.1.4 That correct voltage is supplied to solenoid.

11.1.5 That sufficient air supply is available at inlet to control

block. Inlet pressure to control block should be at least 40
psig for double-acting, 80 psig for spring-return (unless a
reduced spring complement is installed (fewer springs)).
When checking supply pressure, place gauge in line at
control block inlet and monitor gauge for unexpected
pressure drops.

11.2 If proper voltage and air pressure have been verified and

valve is free, proceed as follows:

11.2.1 Turn on signal voltage. Check solenoid for clicking sound.

11.2.2 If no sound is detected, remove air pressure and turn off

signal voltage.

• Carefully unscrew solenoid and solenoid stem from
block.

• Reapply signal voltage and observe solenoid plunger. If
it does not retract, replace solenoid.

11.2.3 If solenoid functions, remove solenoid valve block and

place on bench. Connect to reduced air supply (50 psig)

and correct voltage. Switch signal voltage and check air

flow. Air should flow out only one output port when sole-

noid is energized. The flow should occur only at the other

port when de-energized. (Slight back pressure may be

required to shift the valve spool. This may be generated
by obstructing the outlet ports.)

11.2.4 If control block and solenoid are operating correctly,

proceed to Section 11 below.

11.3 If the actuator functions but exhibits leakage, or power

loss accompanied by leakage, proceed as follows:

11.3 .1 Check voltage. Voltage must be within 10% of the spec-

ified voltage (low voltage will cause leakage out of the
back of the solenoid and burn out the coil).

Actuator

size

Fastening size

Torque

05F39

M5

4Nm

10F39

M6

9Nm

15F39

M6

9Nm

20F39

M8

19Nm

25F39

M8

19Nm

30F39

M10

35Nm

33F39

M10

35Nm

35F39

M12

49Nm

40F39

M12

49Nm

42F39

M16

98NM

45F39

M16

98Nm

45F39

M20

216Nm

STOP!

Advertising