2 remote position indication – Flowserve L120-85 Actuator User Manual

Page 21

Advertising
background image

4.7.2 Remote Position Indication

NOTE: Typical voltmeter remote indicators furnished by Limitorque
are built to accept a maximum of 10 volts. In order to make volt-
meter adjustments, you will need a separate voltmeter with a scale
suitable for the maximum incoming control voltage.

1. Mount the Adjustable Resistor as close as possible to the

Remote Voltmeter Indicator.

2. Turn power to actuator OFF and connect all wiring as shown in

Figure 14. For now, connect the wires leading to the Remote
Voltmeter Indicator to your test meter so you can conduct volt-
age readings during the setup.

3. Move the Adjustable Resistor Slider to the extreme opposite end

of the Resistor from the Power Connection.

4. Open the Electrical Compartment Cover (piece 200-1). Loosen

the Hex Head Retaining Nut at the base of the Potentiometer
Bracket and dis-engage the Spur Gear from the Potentiometer
Drive Gear. This will allow manual rotation of the Potentiometer
Assembly. See figure 14.

5. Manually position the valve in the fully CLOSED position. As

you are rotating the Handwheel to the CLOSED position, notice
the direction the Potentiometer Spur Gear would be turning the
Potentiometer Shaft/Wiper Arm inside the Potentiometer.

6. When the valve is CLOSED, turn the Potentiometer Shaft to the

end-of-travel position that corresponds to the CLOSED position
of the Potentiometer. Carefully reposition the Potentiometer
Spur Gear onto the Potentiometer Shaft to re-engage with the
gear train. Re-tighten Hex Head Retaining Nut at the base of the
Potentiometer Bracket.

c

WARNING: Hazardous Voltage. Use extreme caution
if power is ON and Electrical Compartment Cover is
removed.

7. Turn power to the actuator ON. Your Test Meter should read “0”

or almost “0”. If not, go back through the above steps 1–7 to get
your Potentiometer calibrated to the proper end-of-travel.

8. Now manually position the valve in the fully OPEN position.

9. Move the Adjustable Resistor Slider toward the Power Connec-

tion end until the Test Meter reads 10 volts.

10. Turn actuator power OFF, disconnect the Test Meter and connect

the leads to the Remote Voltmeter Indicator.

11. Turn actuator power ON. Your Remote Voltmeter Indicator

should read full OPEN.

12. Further adjustment may be necessary. If the Remote Voltmeter

Indicator reads less than full OPEN, carefully move the Adjust-
able Resistor Slider ahead being careful not to exceed the full
OPEN position on the Remote Voltmeter Indicator. If the Indica-
tor reads more than “0” when the valve is CLOSED, repeat this
procedure.

13. When the Indicator properly shows valve position, lock the

Adjustable Resistor Slider in place.

Figure 14: Remote Position Indicator Calibration Configuration

P1 P2 P3

CLOSED

Valve Position

1

4

1

2

3

4

OPEN

LIMITORQUE CORPORATION

LYNCHBURG V A.

25 watt, 50 ohm Potentiometer

type Variable Resistor mounted

in a Limitorque Actuator Housing

10.00

Digital Multitester

Control voltage range

110 volts to 480 volts

175 watt, 2500 ohm

Adjustable Resistor

located adjacent to

Remote Position

Indicator for voltage

adjustment

Remote

Voltmeter

Indicator

Ohmmeter

for calibration

Adustable

Resistor Slider

Mounting

Surface

21

Limitorque L120-85 Installation, Operation and Maintenance FCD LMENIM1202-00 – 11/05

flowserve.com

Advertising