Troubleshooting – Flowserve L120-85 Actuator User Manual

Page 35

Advertising
background image

c

WARNING: Be aware of electrical and high-pressure hazards when troubleshooting or performing maintenance
on your L120-85 actuator.

Symptom

Possible Cause

Corrective Action

Unit will not operate electrically

1. No power to unit

1a. Verify electrical supply is phased correctly and present at actuator.
1b. Verify electrical power leads are connected in accordance with the appli-

cable wiring diagram.

1c. Inspect for tripped circuit breaker, overload, open disconnect switch, or

blown fuse.

2. Loose or incorrect wiring

2. Check wiring for proper connections in accordance with the applicable

wiring diagram. Also check for loose connections.

3. Limit Switches not set or incor-

rectly set

3. Check Limit Switch development for agreement with the applicable

wiring diagram. If not set properly, follow instructions for “Setting Limit

Switches”.

4. Foreign material on switch con-

tacts preventing good electrical

contact

4. Check continuity of switches with an ohmmeter.

Motor runs, but no output from unit 1. Actuator not coupled properly to

output

1. Inspect Torque Drive Nut and Valve Shaft to verify key is in place and

properly staked.

2. Torque Drive Nut disengaged

from Drive Sleeve

2. Verify Torque Drive Nut is properly installed in accordance with step 1 of

the Installation Overview.

3. Worm gear worn out

3. Remove Worm Shaft Assembly (following Disassembly Instructions).

Inspect worm gear for unusual wear. If excessive wear has occurred,

replace the Worm Shaft Assembly.

4. Damaged gearing

4. Disassemble actuator following the Disassembly Instructions and

inspect gearing for rough or damaged spots. Replace as required. Most

frequently, damaged spots are seen in motor gear set.

9

Troubleshooting

5

Limitorque L120-85 Installation, Operation and Maintenance FCD LMENIM1202-00 – 11/05

flowserve.com