Basic menu: read, Basic menu: man/aut, Basic menu: shift menu – Flowserve Pulsair III Digital User Manual

Page 12

Advertising
background image

22

Worcester Controls Pulsair III Digital Electronic Positioner FCD WCAIM2056-00 - 08/04

fl owserve.com

23

Worcester Controls Pulsair III Digital Electronic Positioner FCD WCAIM2056-00 - 08/04

Basic Menu: Read

The menu contents are shown in the

fi gures on the right and the steps are

described below:

BASIC MENU
READ

Current values can be read using the Read

Menu and some values can be reset.

Pos Shows current position

Set&pos Set point and position

Set&dev Set point and deviation

Temp Shows current temperature

Aux Shows aux input signal value.

External pot or similar.

Statistics

n cycles Shows number of

movements (turns)

Acc travel Shows accumulated

movement

mean dev Shows accumulated

deviation in %

runtime Shows accumulated

runtime since last reset

extr temp Shows extreme min and

max temperature

Histogram Shows position and time

for PV

Alarms Displays tripped alarms

READ
pos

READ
set&pos

Statistics
n cycles

READ
set&dev

Statistics
acc travel

Statistics
mean dev

Statistics
runtime

Statistics
extr. temp

Statistics
histogram

Statistics
Reset stat

Reset stat
yes

READ
temp

READ
aux

READ
Statistics

READ
Alarms

Reset stat
no

Basic Menu: Man/Aut

The Man/Auto menu is used to change between manual and automatic modes.

BASIC MENU
MAN/AUTO

The menu contents are shown in the fi gures below and the various texts are described

below:

AUT, OK = MAN

Positioner in automatic mode

MAN, OK = AUT

Positioner in manual mode

In the MAN mode, the value of POS can be changed using the up and down arrows. The

pushbuttons increase/decrease the value in steps. The value can also be changed in the

same way as for the other parameter values, as previously described.

Other Functions

C+ can be fully opened by fi rst pressing the up arrow and then immediately OK simulta-

neously.

C- can be fully opened by pressing the down arrow and OK simultaneously.

C+ and C- can be fully opened for blowing clean by pressing the up and down arrows

and OK simultaneously.

When changing between MAN and AUT mode, the OK button must be depressed for

three seconds.

AUT, OK=MAN
SET=12.3%

OK

MAN, OK=AUT
POS=12.3%

Basic Menu: Shift Menu

The Shift Menu is used to choose between the basic menu and the full menu.

BASIC MENU
SHIFT MENU

Advertising