Worcester Controls Pulsair III Digital Electronic Positioner FCD WCAIM2056-00 - 08/04

fl owserve.com

13

Worcester Controls Pulsair III Digital Electronic Positioner FCD WCAIM2056-00 - 08/04

The PULSAIR III Z positioner has an ISO F05 footprint, A. The holes are used to attach it

to the mounting bracket B, which is suitable for most types of linear actuators.

The spindle adapter C can be changed to suit the actuator in question, as previously

explained in this section.

For data for air and electrical connections, see Technical Data section.

Single-Action Positioner (Direct Function)

Actuator with Fail/Close Spring

When the control signal increases, the pressure C+ to the actuator is increased. The

valve stem moves upward and rotates the positioner spindle counterclockwise. When

the control signal drops to zero, C+ is vented and the valve closes.

C–
S
C+

C–
S
C+

Actuator with Fail/Open Spring

When the control signal increases, the pressure C+ to the actuator is decreased. The

springs press the valve stem upward and the positioner spindle rotates counterclock-

wise. When the control signal drops to zero, C+ is vented and the valve opens.

Connections

Air

Port S

Supply air

Port C+ Connection to actuator

Port C-

Connection to actuator (only for
double-action)

C–

S

C+

Must be plugged
when converting
to single-action
function.

Electrical Connection

See Electrical Connections section.

Dimensions

Air connections: ¼

" NPT or G ¼

"

Electrical connection: ½

" NPT or M20 x 1.5

Loctite 577 or equivalent is recommended

as a sealant.

For data for air and electrical connections,

see Technical Data section.