13

Wiring

Bus cable, cable length and size

Note that screened multi-core twisted-pair control cable is required as Bus line, e. g. UNITRONIC

®

BUS

CAN 2 x 2 x ...mm² or RE-2YCYV-fl 2x 2x ...mm².

The cable length dictates the baud rate (data transfer rate) between the bus nodes, and the total power
consumption of the sensor dictates the conductor size.

The baud rate is set via code switch

Fig.4 (S8 to S10). Default factory setting of control unit NRS 1-40.1:

baud rate 250 kBit/s (cable length up to 125 m). For longer cable lengths reduce baud rate accordingly.
Make sure that all bus nodes feature the same settings.

Change baud rate

With lower terminal strip unplugged:
Set the baud rate via code switches

S8 to S10 as specified in the table in section Bus cable, cable length

and size by using a thin blade screwdriver.
Re-insert terminal strip

and fasten the fixing screws

.

Wire terminal strip

Wire terminal strips in accordance with the wiring diagram.

Connect screens only to terminal 3.

The max. baud rates and cable lengths indicated above are based on empirical values ob-
tained by GESTRA. In certain cases it may be necessary to reduce the baud rate in order to
ensure trouble-free operation.

S 8

S 9

S 10

Baud rate

Cable length

Number of pairs

and conductor size [mm²]

OFF

ON

OFF

250 kBit/s

125 m

2 x2 x0.34

Factory setting

ON

ON

OFF

125 kBit/s

250 m

2 x2 x0.5

OFF

OFF

ON

100 kBit/s

335 m

2 x2 x0.75

ON

OFF

ON

50 kBit/s

500 m

available on demand (depends

on bus configuration)

OFF

ON

ON

20 kBit/s

1000 m

ON

ON

ON

10 kBit/s

1000 m

D

D

B

C