Table node id, Decommissioning, Table node id decommissioning – Flowserve NRS1-40.1 User Manual

Page 32: Annex

Advertising
background image

32

Annex

– continued –

Tab le Node ID

In a CAN bus system a maximum of 123 nodes (devices) can be administered. Each node has its own ad-
dress (node ID). This address can be set via a 10-pole code switch

Fig.4.

(Factory setting)

(Example)

Decommissioning

First unplug the terminal strips

,

. For this purpose turn the right and left fixing screws

in direction

of the arrow until the terminal strip can be removed.

Undo the fixing slide in order to snap out the controller and take it off the supporting rail.

Node ID

1

Node ID

71

S1

ON

1

S1

ON

1

S2

OFF

2

S2

OFF

2

S3

OFF

4

S3

ON

4

S4

OFF

8

S4

ON

8

S5

OFF

16

S5

OFF

16

S6

OFF

32

S6

OFF

32

S7

OFF

64

S7

ON

64

S 8

S9

S 10

Baud rate

Cable length

OFF

ON

OFF

250 kBit /s

125 m

Factory setting

ON

ON

OFF

125 kBit /s

250 m

OFF

OFF

ON

100 kBit /s

335 m

ON

OFF

ON

50 kBit /s

500 m

OFF

ON

ON

20 kBit /s

1000 m

ON

ON

ON

10 kBit /s

1000 m

D

ON

1 2 3

5

4

6 7 8 9 10

D

Toggle switch, white

ON

1 2 3

5

4

6 7 8 910

D

Toggle switch, white

A

B

C

Advertising