Fault finding list for level elec trode NRG 1.-40 / control unit NRS 1-40.1

Water level below switchpoint "Low water (LW)" - no low level alarm

Fault:

LED "Power" and LEDs 1 - 4 are not illuminated.

Remedy: Apply mains voltage, wire equipment in accordance with wiring diagram.

Fault:

The electrode rod(s) is/are too long.

Remedy: Cut electrode rod(s) to the length dictated by the switchpoint LW.

Fault:

If the electrode is installed inside the boiler: The vent hole in the protection tube does not exist
or is obstructed.

Remedy: Check installation of level electrode. Make sure that the level in the protection tube corre-

sponds to the actual water level.

Water level not yet below switchpoint "Low water (LW)" - but a low level alarm is raised

Fault:

The electrode rod(s) is/are too short.

Remedy: Replace electrode rod(s) and cut electrode rod(s) to the length dictated by the switchpoint LW.

Fault:

The earth connection to the vessel is interrupted.

Remedy: Clean seating surfaces and screw in the electrode together with the supplied joint ring

∅ 27x32 DIN 7603. Do not insulate the electrode with hemp or PTFE tape!

Fault:

The insulation of the level electrode is faulty.

Remedy: Replace level electrode.