Tools, Basic settings, Factory settings – Flowserve NRS1-40.1 User Manual

Page 16: 16 a, Wiring

Advertising
background image

16

Wiring

– continued –

Wiring diagram for CAN bus system - example -

– continued –

■

Connect screen only to the respective terminals and to the central earthing point (CEP).

■

The rated voltage is indicated on the name plate.

■

When switching off inductive loads, voltage spikes are produced that may impair the op-
eration of control and measuring systems. Connected contactors must therefore be pro-
vided with suppressors such as RC combinations.

■

In the event of an alarm the signal output (terminal 7 and 8) is instantaneously closed.

■

In the event of a malfunction the signal output (terminals 7 and 8) is opened and closed
in a clock-pulse controlled way in order to ensure an optical differentiation between an
alarm and a malfunction signal. If required you can wire terminals 7 and 8 with an exter-
nal signal lamp.

Tools

■

Screwdriver for slotted screws, size 2.5, completely insulated according to VDE 0680-1

■

Screwdriver for cross head screws, size 2

Basic Settings

Fac tory settings

Control unit NRS 1-40.1

The control unit features the following factory set default values:

■

Node ID: 1

■

Baud rate: 250 kBit/s (125 m cable length)

■

De-energizing delay: 3 sec.

■

Configuration: Operation with two level electrodes NRG 1x-40, one level electrode NRG 1x-41.1 and
one temperature transmitter TRV 5-40.