Commissioning

– continued –

Change c onfiguration

– continued –

When determining the limiting functions 1– 4 please take also the installation instructions of
the level electrodes NRG 1x-40, NRG 1x-41.1 and the temperature transmitter TRV 5-40 into
account.

Code switch

Limiting function

S1

S2

S3

S4

S5

S6

1

2

3

4

OFF

OFF

ON

ON

ON

ON

Water level
LW1

ON

ON

ON

ON

ON

ON

Water level
LW1

Water level
LW2

ON

ON

OFF

OFF

ON

ON

Water level
LW1

Water level
LW2

High level
HW

ON

ON

OFF OFF

OFF OFF

Water level
LW 1

Water level
LW 2

High level
HW

Temperature
MAX

Factory setting

ON

ON

OFF

OFF

ON

ON

Water level
LW1

Temperature
MAX 1

Temperature
MAX 2

ON

ON

OFF

OFF

OFF

OFF

Water level
LW1

Water level
LW2

Temperature
MAX 1

Temperature
MAX 2

OFF

OFF

ON

ON

ON

ON

Temperature
MAX1

ON

ON

ON

ON

ON

ON

Temperature
MAX1

Temperature
MAX 2

ON

1 2 3

5

4

6

E

Toggle switch, white

E

Note