AMI Configuration Requirements
The following parameters must set:
• The Advance Control must be enabled on the Global parameter tab.
• Input 8 must be Maintained - Normally Open switch type, and the Clear All function must be
selected. This AMI Input 8 should be wired to Output 8 on the ARC. This input causes the ARC to
reset the AMI message in the event that data communication is lost while an alarm is active.
All other settings regarding the AMI configuration can be project specific.
Specifications
Power Supply Requirements
Connection to a 12 to 24 V dc (UL-listed) Class 2 power source................................... 0.2 amps minimum
Power consumed ................................................................................................................ 2 watts maximum
Electrical
Logic outputs ..................................Sink 100 mA per output to circuit common and must be powered from
an external power supply of the same voltage as the ARC module
Mechanical
Enclosure ................................................................... Steel body and cover, black fine-textured paint finish
Mounting.................................................................................................. Rack-mount, IU Standard, 19-inch
Dimensions ............................................. 19.00 W
× 5.30 D × 1.75 H inches (431 × 135 × 44 mm) nominal
Weight................................................................................................................................................... 5 lbs.
Environmental
Temperature range ................................................................................... +32º F to +122º F (0º C to +50º C)