Equipment required, Test equipment, Documentation – GAI-Tronics ILD1000A Local Deskset User and Installation Manual User Manual

Page 14: Cable installation safety considerations, Electrostatic discharge (esd) protection

Advertising
background image

Installation

ILD1000A Local Desk Set

02/12 10

Equipment Required

Test Equipment

 High-impedance type audio voltmeter with a range of 80 mV

RMS

to 4 V

RMS

capable of measuring

1000 Hz

 #1 Phillips screwdriver
 1/8-inch flat-blade screwdriver
 Optional: RF service monitor

Documentation

 Radio schematics
 Radio manual
 Installation instructions

Cable Installation Safety Considerations

Wiring should conform to the Article 800 of the National Electrical Code. Use listed communication
wiring and cabling for interconnection to other equipment that is suitable for the purpose. Cables should
be marked as

CM

,

CMP

,

CMR

, or

CMX

as appropriate for the use.

Interconnecting data cables should be separated from electrical light or other Class I power cables by at
least 2 inches. The exception is where Class I wiring or power circuits are run in a raceway, or are
metal-sheathed or metal-clad, or are permanently separated from the conductors of the other circuitry by
a continuous and firmly fixed nonconductor, such as porcelain tubes or flexible tubing in addition to the
insulation on the wire. Interconnecting cables longer than 2 meters should be rated VW-1 or FT-1 or
greater. The recommended cable kits conform to these requirements.

Electrostatic Discharge (ESD) Protection

This equipment has ESD protection circuitry which provides a high degree of protection against ESD and
power and telephone line surges. The circuitry shunts the transient currents to earth ground through the
GND terminal.

Terminal 8 inside the desk set on the TS1 terminal block can be used as an earth GND terminal. The
GND terminal must be connected to a high quality earth ground point to obtain maximum protection.

Ideally, the ground point should originate at a 1/2-inch copper rod driven at least 6 feet into the soil with
a No. 16 AWG (or larger) copper wire run to the GND terminal taking the shortest path possible. Where
this is not possible, ground to a nearby water pipe or best available ground.

Advertising