GAI-Tronics MI05-101 Merge / Isolate Cabinet with External Option User Manual

Page 20

Advertising
background image

Pub. MI05-101iom.2

Model MI05-101 Merge/Isolate Cabinet

Page: 20 of 24

\\86h27g1-fs\iomdocs\opnotes -- released\mi05-00x merge-isolate cabs\mi05-101.dir\mi05-101iom2.doc
01/09

Using the 12584-001 AMI I/O Expansion Module

If using the Model 12584-001 I/O Expansion Module with the AMI for additional alarm inputs, the input
screen for each input 9–40 must be programmed.

1. First, program the input Switch Type and the Current Message to be activated by the input.

2. Next, program the Current Output Combination to

Output 1

. This will cause output 1 to activate

while the input is active. The M/I cabinet will merge all zones during the alarm message as a result
of the active output.

Inputs 9–40 are independent of the Master Station and will be automatically broadcast to all zones of the
system. The following screen is an example of Input 9. Remaining inputs 10–40 must be programmed in
the same fashion if used.