X. program settings – Greenheck Melink IH3 Operations User Manual

Page 14

Advertising
background image

X. Program

Settings

Below is a list of program settings for Intelli‐Hood.  Please reference the Program Settings 

Explanation Manual for additional details. 

 

Parameter 

Default Value 

Range of Values 

Hood Controller Parameters 

  

HCxx‐01 

Hood Network Address 

0 To 39 

HCxx‐02 

Name 

HC‐x 

Up to 20 Characters 

HCxx‐03 

Optic Sensor 

Yes 

Yes or No 

HCxx‐04 

Temp Channel 1 

Hood 

No, Hood, Auto Only, Supply, Space 

HCxx‐05 

Temp Channel 1 Span Max. (°F) 

90 

50F To 200F (Increments Of 5F) 

HCxx‐06 

Temp Channel 2 

No 

No, Hood, Auto Only, Supply, Space 

HCxx‐07 

Temp Channel 2 Span Max. (°F) 

Match Channel 1 

50F To 200F (Increments Of 5F), Match Channel 1 

HCxx‐08 

Temp Channel 3 

No 

No, Hood, Auto Only, Supply, Space 

HCxx‐09 

Temp Channel 3 Span Max. (°F) 

Match Channel 1 

50F To 200F (Increments Of 5F), Match Channel 1 

HCxx‐10 

Temp Channel 4 

No 

No, Hood, Auto Only, Supply, Space 

HCxx‐11 

Temp Channel 4 Span Max. (°F) 

Match Channel 1 

50F To 200F (Increments Of 5F), Match Channel 1 

HCxx‐12 

Temp Actual Channel 1 

Measured Temp 

User Inputs Actual Temperature 0 To 500F 

HCxx‐13 

Temp Actual Channel 2 

Measured Temp 

User Inputs Actual Temperature 0 To 500F 

HCxx‐14 

Temp Actual Channel 3 

Measured Temp 

User Inputs Actual Temperature 0 To 500F 

HCxx‐15 

Temp Actual Channel 4 

Measured Temp 

User Inputs Actual Temperature 0 To 500F 

HCxx‐16 

Temp Channel 1 Span Min. (°F) 

75 

50F to 90F (Increments of 1F) 

HCxx‐17 

Temp Channel 2 Span Min. (°F) 

Match Channel 1 

50F to 90F (Increments of 1F), Match Channel 1 

HCxx‐18 

Temp Channel 3 Span Min. (°F) 

Match Channel 1 

50F to 90F (Increments of 1F), Match Channel 1 

HCxx‐19 

Temp Channel 4 Span Min. (°F) 

Match Channel 1 

50F to 90F (Increments of 1F), Match Channel 1 

HCxx‐20 

Optic Smoke Density 

Medium 

Low, Medium, or High 

  

  

  

  

Exhaust Hood Parameters 

  

EHxx‐01 

Primary Exhaust ID 

1 to 39 

EHxx‐02 

Name 

Hood x 

Up To 20 Characters 

EHxx‐03 

Minimum Speed 

50% 

30% To 100%, Increments Of 5% 

EHxx‐04 

Maximum Speed 

100% 

30% To 100%, Increments Of 5% 

EHxx‐05 

Select Hood Controllers 

None Selected 

0 to 39 

EHxx‐06 

Temperature Sensor Node(s) 

  

00‐1 to 39‐4 

EHxx‐07 

Optic Sensor Node(s) 

  

00 to 39 

EHxx‐08 

Auto On Hood Temperature 

Auto On 120F 

Not Used, Auto On 70F ‐ 120F 

EHxx‐09 

Auto On Space Differential 

Not Used 

Not Used, Room Difference +1F ‐ +40F 

EHxx‐10 

Auto Off Hood Temp 

Not Used 

Not Used, Auto Off 65F ‐ 100F 

EHxx‐11 

Auto Off Space Differential 

Not Used 

Not Used, Room Difference +1F ‐ +20F 

EHxx‐12 

Auto On/Off Grouping 

Yes 

Yes Or No 

EHxx‐13 

Digital Inputs To Utilize 

Select All 

DI 1, DI 2, DI 3 

EHxx‐14 

Digital Outputs To Affect 

Select All 

Relay 1, Relay 2, 24VDC 1, 24VDC 2 

EHxx‐15 

Temperature Alarm Auto On 

System 

Not Used, System, 100F, 125F, 150F, 200F, 250F, 
300F  

EHxx‐16 

Short Cycle Ratio 

Not Used 

Not Used, 20%, 30%, 40%, 50%, 60%, 70%, 80% 

EHxx‐17 

User Interface On/Off 

TP1 

None, Touchpad 1‐10, Aux Touchpad 0‐9 

EHxx‐18 

Exhaust CFM 

1000 

0 to 100,000 

EHxx‐19 

Groups 

1‐10 

EHxx‐20 

Touchpad Display Node 

1‐10 

EHxx‐21 

Optic Hang time 

System 

System, 5, 10, 15, 30, 45, 60, 120, 180, 300 

  

  

  

  